Delta C2000 series User Manual page 252

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Settings
Functions
46
Master dEb signal output
47
Brake Release at Stop
48
Reserved
49
Homing Action Complete Output when homing action complete.
Output for CANopen
50
control
Output for
51
communication card
52
Output for RS-485
53~62 Reserved
Chapter 12 Description of Parameter Settings|C2000 Series
level except 0 and set Pr.07-02 = T2 (DC brake time at start up)
and Pr.07-03 = T2 (DC brake current at stop). It is recommend to
set T2 >T1 and try to activate brake control during zero-speed
status.
AC Driver
U(T1)
V(T2)
W(T3)
When dEb arise at Master, MO will send a dEb signal to Slave. Then
Slave will follow Master's command and decelerate to stop
simultaneously.
When drive stops, the corresponding multi-function terminal will
be ON if the frequency is less than Pr.02-34. After it is ON, it will
be OFF when brake delay time exceeds Pr.02-32.
Output Freq uency
RUN
M ulti-function
Output
M O=d 47
For CANopen communication output
For
communication
(CMC-MOD01, CMC-EIP01, CMC-PN01 and CMC-DN01)
For RS-485 output
12-45
Descriptions
MC
MOx=45
MIx=49
Output Freq uency
< Pr.02-34
RUN
02 -3 2
output
of
communication
Motor
IM
3~
Tim e
cards