User Defined Value; Local/Remote Selection - Delta C2000 series User Manual

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

User define is enabled when Pr.00-26 is not 0. The setting of Pr.00-26 corresponds to Pr.01.00
(Max. output frequency of the drive).
Example: User define: 100.0%, Pr.01.00 = 60.00Hz
Pr.00.25 setting is 0021h; Pr.0026 setting is 100.0%
NOTE
The drive will display as Pr.00-25 setting when Pr.00-25 is properly set and Pr.00-26 is not 0.

User Defined Value

Settings Read only
Pr.00-27 will show user defined value when Pr.00-26 is not set to 0.
User defined function is valid when Pr.00-20 is set to digital keypad control or RS-285
communication input control.
Reserved

LOCAL/REMOTE Selection

Settings 0: Standard HOA function
The factory setting of Pr.00-29 is 0 (standard Hand-Off-Auto function). The AUTO frequency and
source of operation can be set by Pr.00-20 and Pr.00-21, and the HAND frequency and source of
operation can be set by Pr.00-30 and Pr.00-31. AUTO/HAND mode can be selected or switched by
using digital keypad(KPC-CC01) or setting multi-function input terminal MI= 41, 42.
When external terminal MI is set to 41 and 42 (AUTO/HAND mode), the settings Pr.00-29=1,2,3,4
will be disabled. The external terminal has the highest priority among all command, Pr.00-29 will
always function as Pr.00-29=0, standard HOA mode.
When Pr.00-29 is not set to 0, Local/Remote function is enabled, the top right corner of digital
keypad (KPC-CC01) will display "LOC" or "REM" (the display is available when KPC-CC01 is
installed with firmware version higher than version 1.021). The LOCAL frequency and source of
operation can be set by Pr.00-20 and Pr.00-21, and the REMOTE frequency and source of
operation can be set by Pr.00-30 and Pr.00-31. Local/Remote function can be selected or switched
by using digital keypad(KPC-CC01) or setting external terminal MI=56. The AUTO key of the digital
keypad now controls for the REMOTE function and HAND key now controls for the LOCAL
function.
When MI is set to 56 for LOC/REM selection, if Pr.00-29 is set to 0, then the external terminal is
0.0~6553.5 (when Pr.00-25 set to 1 decimal place)
0.0~655.35 (when Pr.00-25 set to 2 decimal place)
0.0~65.535 (when Pr.00-25 set to 3 decimal place)
1: Switching Local/Remote, the drive stops
2: Swithcing Local/Remote, the drive runs as the REMOTE setting for
frequency and operation status
3: Swithcing Local/Remote, the drive runs as the LOCAL setting for frequency
and operation status
4: Swithcing Local/Remote, the drive runs as LOCAL setting when switch to
Local and runs as REMOTE setting when switch to Remote for frequency
and operation status.
Chapter 12 Description of Parameter Settings|C2000 Series
12-15
Factory Setting: Read only
Factory Setting: 0