Display
Fault code
Fault
ovS
Ov at stop
Fault
LvA
Lv at accel
Fault
Lvd
Lv at decel
Fault
Lvn
Lv at normal SPD
Fault
LvS
Lv at stop
Fault
OrP
Phase La cked
Fault
oH1
IGBT over heat
Fault
oH2
Hear Sink oH
Fault
tH1o
Thermo 1 open
Fault
tH2o
Thermo 2 open
Over-voltage at stop. Hardware failure in
000AH
current detection
DC BUS voltage is less than Pr.06.00
000BH
during acceleration.
DC BUS voltage is less than Pr.06.00
000VH
during deceleration.
DC BUS voltage is less than Pr.06.00 in
000DH
constant speed.
DC BUS voltage is less than Pr.06-00 at
000EH
stop
000FH
Phase Loss Protection
IGBT overheat
IGBT temperature exceeds protection
level.
0010H
1~15HP: 90℃
20~100HP: 100℃
Heatsink overheat
0011H
Heat sink temperature exceeds 90oC
Temperature detection circuit error
0012H
(IGBT)
IGBT NTC
Temperature detection circuit error
0013H
(capacity module)
CAP NTC
15-24
Chapter 15 CANopen Overview |C2000 Series
Description
CANopen
CANopen
fault
fault code
register
(bit 0~7)
3210H
2
3220H
2
3220H
2
3220H
2
3220H
2
3130H
2
4310H
3
4310H
3
FF00H
3
FF01H
3