Figure 3

Function of DC Link

Applicable to Frame E~H
Operation Instruction
1. When RST power is off, please disconnect terminal r and terminal s. (As circled in dotted line,
uninstall the gray section and properly store cable r and cable s. Cable r and cable s are not
available in optional accessories, do not dispose them.)
After terminal r and terminal s are cleared, user may now connect new power source to terminal r
and terminal s. Please connect 220Vac for 220V model and 440 Vac for 440V model.
When the drive power is on, if terminal r and terminal s are not connected to new power source
(220 Vac for 220V model and 440Vac for 440 V model), the digital keypad will display an error
message "ryF".
2. When DC Link is used as a DC Bus connection (RST power is applied), it is not required to
remove terminal r and terminal s.
NOTE
Common DC Bus can only be applied to the drives with same power range. If in your case the
drives are in different power range, please contact with us (Delta Industrial Automation Business
Unit).
r s
4-5
Chapter 4 Wiring|C2000 Series