Ov er-Curr ent
D etec tion Level
06-04
over- curr ent stall pr eventi on during oper ation
Accel./Decel. Time Selection of Stall Prevention at Constant Speed
Settings 0: by current accel/decel time
1: by the 1st accel/decel time
2: by the 2nd accel/decel time
3: by the 3rd accel/decel time
4: by the 4th accel/decel time
5: by auto accel/decel
It is used to set the accel./decel. time selection when stall prevention occurs at constant speed.
Over-torque Detection Selection (OT1)
Settings 0: Disable
1: Over-torque detection during constant speed operation, continue to
operate after detection
2: Over-torque detection during constant speed operation, stop operation
after detection
3: Over-torque detection during operation, continue to operate after detection
4: Over-torque detection during operation, stop operation after detection
Over-torque Detection Selection (OT2)
Settings 0: Disable
1: Over-torque detection during constant speed operation, continue to
operate after detection
2: Over-torque detection during constant speed operation, stop operation
after detection
3: Over-torque detection during operation, continue to operation after
detection
4: Over-torque detection during operation, stop operation after detection
Chapter 12 Description of Parameter Settings|C2000 Series
Ov er-C urr ent Stall P revention
during Operation, output
frequency dec reases
D ecreases by
deceleration t ime
12-96
Pr . 06-04 s etting
Current
Pr . 06-04 s et ting-
rated dr ive c urrent X 5%
Output
F requenc y
T ime
Factory Setting: 0
Factory Setting: 0
Factory Setting: 0