Fan Cooling Control; Emergency Stop (Ef) & Force Stop - Delta C2000 series User Manual

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Settings 0.00~600.00Hz
Dwell Time at Decel.
Settings 0.00~600.00 sec
Dwell Frequency at Decel.
Settings 0.00~600.00 Hz
In the heavy load situation, Dwell can make stable output frequency temporarily, such as crane or
elevator.
Pr.07-15 to Pr.07-18 is for heavy load to prevent OV or OC occurs.
Frequency
07-16
Dwell
Frequency
at Accel.

Fan Cooling Control

Settings 0: Fan always ON
1: 1 minute after the AC motor drive stops, fan will be OFF
2: When the AC motor drive runs, the fan is ON. When the AC motor drive
stops, the fan is OFF
3: Fan turns ON when preliminary heat sink temperature (around 60
attained.
4: Fan always OFF
This parameter is used for the fan control.
Setting 0: Fan will be ON as the drive's power is turned ON.
Setting 1: 1 minute after AC motor drive stops, fan will be OFF
Setting 2: AC motor drive runs and fan will be ON. AC motor drive stops and fan will be OFF.
Setting 3: Fan run according to IGBT and capacitance temperature. Fan will be ON when
preliminary capacitance temperature is higher than 60oC. Fan will be OFF, when capacitance
temperature is lower than 40oC.
Setting 4: Fan is always OFF
Emergency Stop (EF) & Force Stop
0: Coast to stop
Settings
1: Stop by 1
2: Stop by 2
3: Stop by 3
Chapter 12 Description of Parameter Settings|C2000 Series
07-15
Dwell Time
at Accel.
Dwell at accel./decel.
st
deceleration time
nd
deceleration time
rd
deceleration time
12-121
Factory Setting: 0.00
Factory Setting: 0.00
07-18
Dwell
07-17
Frequency
Dwell Time
at Decel.
at Decel.
Factory Setting: 0
Factory Setting: 0
Time
o
C) is