03 Analog Input / Output Parameters

Pr.
Parameter Name
03-00
Analog input selection (AVI1)
03-01
Analog input selection (ACI)
03-02
Analog input selection (AVI2)
03-03
Analog input bias (AVI1)
03-04
Analog input bias (ACI)
Analog positive voltage input
03-05
bias (AVI2)
Positive / negative bias mode
03-07
(AVI1)
Positive / negative bias mode
03-08
(ACI)
Positive / negative bias mode
03-09
(AVI2)
Reverse setting when analog
 03-10
signal input is negative
frequency
03-11
Analog input gain (AVI1)
03-12
Analog input gain (ACI)
03-13
Analog positive input gain (AVI2)
Analog negative input gain
03-14
(AVI2)
03-15
Analog input filter time (AVI1)
03-16
Analog input filter time (ACI)
03-17
Analog input filter time (AVI2)
03-18
Analog input addition function
Signal loss selection for
03-19
analog input 4–20 mA
03-20
Multi-function output 1 (AFM1)
03-23
Multi-function output 2 (AFM2)
Setting Range
0: No function
1: Frequency command (speed limit under torque
control mode)
4: PID target value
5: PID feedback signal
6: Thermistor (PTC) input value
11: PT100 thermistor input value
13: PID compensation value
-100.0–100.0%
0: No bias
1: Lower than or equal to bias
2: Greater than or equal to bias
3: The absolute value of the bias voltage while serving
as the center
4: Bias serves as the center
0: Negative frequency is not allowed. The digital
keypad or external terminal controls the forward and
reverse direction.
1: Negative frequency is allowed. Positive frequency =
run in forward direction; negative frequency = run in
reverse direction. The digital keypad or external
terminal control cannot switch the running direction.
-500.0–500.0%
0.00–20.00 sec.
0: Disable (AVI1, ACI, AVI2)
1: Enable
0: Disable
1: Continue operation at the last frequency
2: Decelerate to 0 Hz
3: Stop immediately and display ACE
0: Output frequency (Hz)
1: Frequency command (Hz)
2: Motor speed (Hz)
3: Output current (rms)
4: Output voltage
5: DC bus voltage
11-14
Default
1
0
0
0.0
0
0
100.0
0.01
0
0
0
0