Analog Input / Output Parameters - Delta ME300 Series User Manual

Basic compact drive
Hide thumbs Also See for ME300 Series:
Table of Contents

Advertisement

03 Analog Input / Output Parameters

03-00
Analog Input Selection (AI)
Settings
 When you use analog input as the PID reference target input, you must set Pr.00-20 to 2
(external analog input).
Setting method 1: Pr.03-00 set 1 as frequency command.
Setting method 4: Pr.03-00 set 4 as PID reference target input.
 When you use analog input as the PID compensation value, you must set Pr.08-16 to 1 (source
of PID compensation value is analog input). You can see the compensation value with Pr.08-17.
 When you use the frequency command, the corresponding value for 0– ±10 V / 4–20 mA is 0–
maximum operation frequency (Pr.01-00).
03-03
Analog Input Bias (AVI)
Settings
 Sets the corresponding AVI voltage for the external analog input 0.
03-04
Analog Input Bias (ACI)
Settings
 Sets the corresponding ACI voltage for the external analog input 0.
03-07
Positive / Negative Bias Mode (AVI)
03-08
Positive / Negative Bias Mode (ACI)
Settings
 In a noisy environment, use negative bias to provide a noise margin. Do NOT use less than 1 V
to set the operation frequency.
0: No function
1: Frequency command
4: PID target value
5: PID feedback signal
6: Thermistor (PTC) input value
11: PT100 thermistor input value
12: Auxiliary frequency input
13: PID compensation value
-100.0–100.0%
-100.0–100.0%
0: No bias
1: Lower than or equal to bias
2: Greater than or equal to bias
3: The absolute value of the bias voltage while serving as the center
4: Bias serves as the center
12.1-03-1
Chapter 12 Description of Parameter SettingsME300
this parameter during operation.
You can set
Default: 1
Default: 0
Default: 0
Default: 0