03 Analog Input / Output Parameter
AVI Analog Input Selection
03-00
ACI Analog Input Selection
03-01
AUI Analog Input Selection
03-02
Settings 0: No function
 When you use analog input as the PID reference target input, you must set Pr.00-20 to 2 (external
analog input).
Setting method 1: Pr.03-00–03-02 set 1 as Frequency command.
Setting method 2: Pr.03-00–03-02 set 4 as PID reference target input.
If the setting value 1 and setting value 4 exist at the same time, the AVI input has highest priority
to become the PID reference target input value.
 When you use analog input as the PID compensation value, you must set Pr.08-16 to 1 (source
of PID compensation value is analog input). You can see the compensation value with Pr.08-17.
 When using the Frequency command or TQC speed limit, the corresponding value for 0–±10 V /
4–20 mA is 0–maximum operation frequency (Pr.01-00).
 When using the torque command or torque limit, the corresponding value for 0–±10 V / 4–20 mA
is 0–maximum output torque (Pr. 11-27).
 When using the torque compensation, the corresponding value for 0–±10 V / 4–20m A is 0–the
motor's rated torque.
 The analog input AVI / ACI (use with Switch terminal to switch SW2 to 0–10V) supports KTY84.
The AUI does not support this function.
 When you use KTY84, you can only choose either AVI or ACI at the same time. The AVI is prior to
ACI.
 If the settings for Pr.03-00–Pr.03-02 are the same, the AVI input has highest priority.
1: Frequency command (speed limit under torque control mode)
2: Torque command (torque limit under speed control mode)
3: Torque compensation command
4: PID target value
5: PID feedback signal
6: Thermistor (PTC / KTY-84) input value
7: Positive torque limit
8: Negative torque limit
9: Regenerative torque limit
10: Positive / negative torque limit
11: PT100 thermistor input value
13: PID compensation value
12.1-03-1
Chapter 12 Descriptions of Parameter SettingsC2000 Plus
 You can set this parameter during operation.
Default: 1
Default: 0
Default: 0