Chapter 3 Set Up the VFD Parameters | CP2000

Digital Input / Output Parameters (02) group

Parameter
Display Text
02-35 External
Fault Reset OP
operation after
reset and activate

Motor Parameters (05) group

Parameter
Display Text
05-01 Full load
Motor 1 Rated
current of motor
A
05-02 Rated
Motor 1 Rated
power of motor
P
05-03 RPM of
Motor 1 Rated
motor
05-04 Number of
Motor 1 Poles
poles in motor
Description of Parameter
When set to 1, the drive
automatically restarts after a
power failure, assuming the
FWD terminal is still closed.
When set to 0, the drive
powers up again and stops,
requiring a cycle of the Start
signal (turn off and then turn
on again) to resume normal
operation (Value 0 is not
recommended).
Description of Parameter
This determines the full load
rating of the motor in amps.
This determines the motor
power in kW.
This determines the motor's
60Hz RPM.
This determines the motor's
number of poles.
Parameter options:
2 – 3600 RPM
4 – 1800 RPM
6 – 1200 RPM
8 – 900 RPM
10
Default
Preferred
Value
Value
0
1
Default
Preferred
Value
Value
None
As stated
on the
motor
nameplate.
None
As stated
on the
motor
nameplate.
Note: kW
= HP *
0.746
1710 RPM.
As stated
This is fine
on the
for 4 pole
motor
motors.
nameplate.
4, which is
RPM value
correct for
as stated
~1800 RPM
on the
motors.
motor
nameplate.