Key Points for Adjustment
Select the adjustment method referring to the following points.
When the measurement results are unstable
Searching other positions
Parameter to be adjusted
Model parameter
Measurement
The judgement is NG (insufficient memory)
Parameter to be adjusted
Region setting
Model parameter
When the processing speed is slow
Parameter to be adjusted
Region setting
Model
Model parameter
Measurement
FH/FZ5 Processing Item Function Reference Manual
Specify a larger value for the "Prec."
If the measurement results are unstable only when "Rotation" is selected, specify a smaller
value for the "Skipping angle".
When "Rotation" is selected, if the model shape is complex, uncheck the "Smart mode" option.
If the image has low contrast or blurred edges, set the "Search mode" to "CR".
If the model image consists of detailed figures, specify a larger value for "Stab."
If the precision is low, place a check at "Sub-pixel".
If images that should be judged OK vary greatly, specify a smaller value for "Candidate level".
If the model image is small and unstable, specify a smaller value for the "Reduction".
Make the search region as small as possible.
Bring "Stab." close to the factory default value.
Bring the "Skipping angle" close to the factory default value.
Specify a smaller value for "Prec.".
Make the search region as small as possible.
Make the area to register as the model as small as possible.
If the model image is a simple figure or a large figure, specify a smaller value for "Stab." If
lowering stability does not speed up processing, it is likely that many candidates have been
detected. Raise the "Candidate level" in [Measurement].
When "Rotation" is selected and the model image is a simple figure, specify a larger value for
"Skipping angle".
When "Rotation" is selected and the model image is a simple figure, place a check at "Smart
mode".
If the position precision is high, specify a smaller value for "Prec.".
If the rotation angle range is large, set the "Search mode" to "PT".
If images that should be judged OK vary little, specify a larger value for "Candidate level".
If the position precision is high, uncheck "Sub-pixel".
Remedy
Remedy
Remedy
2
221
Classification