Key Points for Adjustment
Select the adjustment method referring to the following points.
When the measurement results are unstable
Searching other positions
Parameter to be adjusted
Model parameter
Sub-model parameter
Measurement
The judgement is NG (insufficient memory)
Parameter to be adjusted
Region setting
Model parameter
Sub-model parameter
When the processing speed is slow
Parameter to be adjusted
Region setting
Model Registration
Model parameter
Sub-model parameter
Measurement parameter
128
Sensitive Search
Specify a larger value for the "Prec."
If the measurement results are unstable only when "Rotation" is selected, specify a smaller
value for the "Skipping angle".
When "Rotation" is selected, if the model shape is complex, uncheck the "Smart mode" option.
If the model image consists of detailed figures, specify a larger value for "Stab."
If images that should be judged OK vary greatly, specify a larger value for "Sub-model number
X" and "Sub-model number Y".
If the precision is low, place a check at "Sub-pixel".
If images that should be judged OK vary greatly, specify a smaller value for "Candidate level".
If images that should be judged OK vary greatly, specify a larger value for "Sub-region margin".
Make the search region as small as possible.
Bring "Stab." close to the factory default value.
Bring the "Skipping angle" close to the factory default value.
Specify a smaller value for "Prec.".
Specify a larger value for "Sub-model number X" and "Sub-model number Y".
Make the search region as small as possible.
Make the area to register as the model as small as possible.
If the model image is a simple figure or a large figure, specify a smaller value for "Stab." If
lowering stability does not speed up processing, it is likely that many candidates have been
detected. Raise the "Candidate level" in [Measurement].
When "Rotation" is selected and the model image is a simple figure, specify a larger value for
"Skipping angle".
When "Rotation" is selected and the model image is a simple figure, place a check at "Smart
mode".
If the position precision is high, specify a smaller value for "Prec.".
If images that should be judged OK vary greatly, specify a larger value for "Sub-model number
X" and "Sub-model number Y".
If images that should be judged OK vary little, specify a larger value for "Candidate LV".
If the position precision is high, uncheck "Sub-pixel".
Remedy
Remedy
Remedy