show inlets <n> details
Variables:
•
•
<n> is one of the options: all, or a number.
Option
Description
all
Displays the information for all inlets.
Tip: You can also type the command without adding this
option "all" to get the same data.
A specific
Displays the information for the specified inlet only.
inlet number
An inlet number needs to be specified only when there are more
than 1 inlet on your PDU.
Displayed information:
•
•
Without the parameter "details," only the inlet's name and RMS current are displayed.
•
•
With the parameter "details," more inlet information is displayed in addition to the inlet name and
RMS current, such as the inlet's RMS voltage, active power and active energy.
Overcurrent Protector Information
This command is only available for models with overcurrent protectors for protecting outlets.
This command syntax shows the overcurrent protector information, such as a circuit breaker or a fuse.
#
show ocp <n>
To show detailed information, add the parameter "details" to the end of the command.
#
show ocp <n> details
Variables:
•
•
<n> is one of the options: all, or a number.
Option
Description
all
Displays the information for all overcurrent protectors.
Tip: You can also type the command without adding
this option "all" to get the same data.
337
Need help?
Do you have a question about the Server Technology PRO3X and is the answer not in the manual?