Individual Sensor/Actuator Pages - LEGRAND Server Technology PRO3X User Manual

Hide thumbs Also See for Server Technology PRO3X:
Table of Contents

Advertisement

• Select "Automatically assign a sensor number" to assign an unused ID number. This method does
not release any managed sensor or actuator.
• Select "Manually select a sensor number" to select a desired ID number from the list. Selecting an
ID already in use will release the sensor currently managed with that ID. IDs already in use show
the sensor package's serial number. Available IDs show "unused."
4) Click Manage.
Special note for Legrand humidity sensors:
A Legrand humidity sensor is able to provide two measurements - relative and absolute humidity
values.
A relative humidity value is measured in percentage (%).
An absolute humidity value is measured in grams per cubic meter (g/m
However, only relative humidity sensors are "automatically" managed if the automatic management
function is enabled. You must "manually" manage absolute humidity sensors as needed.
Note: Relative and absolute values of the same humidity sensor do NOT share the same ID number
though they share the same serial number and position.

Individual Sensor/Actuator Pages

A sensor's or actuator's data/setup page is opened after clicking any sensor or actuator name on the
Peripheral Devices page.
Note that only a numeric sensor has threshold settings, while a state sensor or actuator has no
thresholds.