LEGRAND Server Technology PRO3X User Manual page 101

Hide thumbs Also See for Server Technology PRO3X:
Table of Contents

Advertisement

Settings--Reset energy counter:
The energy counter reset feature per inlet is especially useful when your PRO3X has more than one
inlet. Only users with the "Admin" role assigned can reset this value.
Click Reset and then confirm in the message.
This inlet's active energy reading is then reset to zero.
Tip: To reset ALL active energy counters on the PRO3X, go to the PDU page.
Settings: Reset minimum/maximum:
All inlet sensors with numeric readings store their minimum and maximum recorded reading. You can
reset these as desired. Only users with the "Admin" role assigned can reset this value.
Tip: To enable the display of minimum/maximum for any sensor, click the
right of the Sensors lists.
Click Reset and then confirm in the message.
This inlet's sensor's minimum and max values are reset.