LEGRAND Server Technology PRO3X User Manual page 330

Hide thumbs Also See for Server Technology PRO3X:
Table of Contents

Advertisement

Example 1 - Combination of ETH1's Activation, Configuration Method and IP
The following multi-command syntax configures IPv4 address, configuration method and activation
status for ETH1's network connectivity simultaneously.
config:# network ipv4 interface eth1 enabled true configMethod static
address 192.168.84.225/24
Results:
The ETH1 interface is enabled.
ETH1's configuration method is set to static IP address.
ETH1's IPv4 address is set to 192.168.84.225/24.
Example 2 - Combination of Upper Critical and Upper Warning Settings
The following multi-command syntax simultaneously configures Upper Critical and Upper Warning
thresholds for the RMS current of the 2nd overcurrent protector.
config:#
sensor ocp 2 current upperCritical disable upperWarning 15
Results:
The Upper Critical threshold of the 2nd overcurrent protector's RMS current is disabled.
The Upper Warning threshold of the 2nd overcurrent protector's RMS current is set to 15A and
enabled at the same time.
Example 3 - Combination of SSID and PSK Parameters
This multi-command syntax configures both SSID and PSK parameters simultaneously for the wireless
feature.
config:#
network wireless SSID myssid PSK encryp_key
Results:
The SSID value is set to myssid.
The PSK value is set to encryp_key.
Example 4 - Combination of Upper Critical, Upper Warning and Lower Warning Settings
The following multi-command syntax configures Upper Critical, Upper Warning and Lower Warning
thresholds for the outlet 5 RMS current simultaneously.
330