Operation:
1) Choose Device Settings > Event Rules >
2) Select 'Change load shedding state' from the Action list.
3) In the Operation field, select either one below:
• Start load shedding: Enters the load shedding mode when the specified event occurs.
•
•
• Stop load shedding: Quits the load shedding mode when the specified event occurs.
External Beeper
If an external beeper is connected, you can change the beeper's behavior or status to respond to a
certain event.
▶
To control the connected external beeper:
1) Choose Device Settings > Event Rules >
2) Select 'External beeper' from the Action list.
3) In the 'Beeper port' field, select the port where the external beeper is connected.
4) In the 'Beeper action' field, select an action for the external beeper to carry out.
• Alarm: Causes the external beeper to sound an alarm cycle every 20 seconds - stays on for 0.7
•
seconds and then off for 19.3 seconds.
• On: Turns on the external beeper so that it buzzes continuously.
•
• Off: Turns off the external beeper so that it stops buzzing.
•
Warning: If you create an event rule for the external beeper but disconnect it when an event causes it
to beep, the beeper no longer beeps after it is re-connected even though the event triggering the
beeping action remains asserted.
Internal Beeper
You can have the built-in beeper of the PRO3X turned on or off when a certain event occurs.
▶
Operation:
1) Choose Device Settings > Event Rules >
2) Select 'Internal beeper' from the Action list.
3) Select an option from the Operation field.
•
• Turn beeper on: Turns on the internal beeper to make it buzz.
•
• Turn beeper off: Turns off the internal beeper to make it stop buzzing.
Log an Event Message
The option 'Log event message' records the selected events in the internal log.
A default log message will be generated for each type of event, or you can create a custom log message.
.
.
.
241