Variables:
<n> is the ID number of the environmental sensor that you want to configure. The ID number is
available in the PRO3X web interface or using the command "show externalsensors <n>" in
the CLI. It is an integer starting at 1.
<time> is an integer number in seconds, ranging between 0 and 300.

Configuring Environmental Sensors' Default Thresholds

You can set the default values of upper and lower thresholds, deassertion hysteresis and assertion
timeout on a sensor type basis, including temperature, humidity, air pressure and air flow sensors. The
default thresholds automatically apply to all environmental sensors that are newly detected or added.
A default threshold configuration command begins with defaultThresholds.
You can configure various default threshold settings for the same sensor type at a time by combining
multiple commands.
Set the Default Upper Critical Threshold for a specific sensor type:
config:# defaultThresholds <sensor type> upperCritical <value>
Set the Default Upper Warning Threshold for a specific sensor type:
config:#
defaultThresholds <sensor type> upperWarning <value>
Set the Default Lower Critical Threshold for a specific sensor type:
config:# defaultThresholds <sensor type> lowerCritical <value>
Set the Default Lower Warning Threshold for a specific sensor type:
config:#
defaultThresholds <sensor type> lowerWarning <value>
Set the Default Deassertion Hysteresis for a specific sensor type:
config:# defaultThresholds <sensor type> hysteresis <hy_value>
443