config:# externalsensor <n> description "<description>"
Variables:
•
•
<n> is the ID number of the environmental sensor that you want to configure. The ID number is
available in the web interface or using the command "show externalsensors <n>" in the
CLI. It is an integer starting at 1.
•
•
<description> is a string comprising up to 64 ASCII printable characters, and it must be enclosed in
quotes when it contains spaces.
Using Default Thresholds
This command determines whether default thresholds, including the deassertion hysteresis and
assertion timeout, are applied to a specific environmental sensor.
config:#
externalsensor <n> useDefaultThresholds <option>
Variables:
•
•
<n> is the ID number of the environmental sensor that you want to configure. The ID number is
available in the PRO3X web interface or using the command "show externalsensors <n>" in
the CLI. It is an integer starting at 1.
•
•
<option> is one of the options: true or false.
Option Description
true
Default thresholds are selected as the threshold option for the specified
sensor.
false
Sensor-specific thresholds are selected as the threshold option for the
specified sensor.
Setting the Alarmed to Normal Delay for DX2-passive infrared sensor
This command determines the value of the Alarmed to Normal Delay setting for a Server Technology
presence detector.
config:#
externalsensor <n> alarmedToNormalDelay <time>