Variables:
•
•
<n> is the environmental sensor number. The environmental sensor number is the ID number
assigned to the sensor, which can be found on the Peripherals page of the PRO3X web interface.
Displayed information:
•
•
Without the parameter "details," only the reading, threshold, deassertion hysteresis and assertion
timeout settings of the specified environmental sensor are displayed.
•
•
With the parameter "details," more sensor information is displayed, including resolution and range.
Note: For a state sensor, the threshold-related and accuracy-related data is NOT available.
Environmental Sensor Default Thresholds
This command syntax shows a certain sensor type's default thresholds, which are the initial thresholds
applying to the specified type of sensor.
# show defaultThresholds <sensor type>
To show detailed information, add the parameter "details" to the end of the command.
# show defaultThresholds <sensor type> details
Variables:
•
•
<sensor type> is one of the following numeric sensor types:
Sensor types
Description
absoluteHumidity Absolute humidity sensors
relativeHumidity
Relative humidity sensors
temperature
Temperature sensors
airPressure
Air pressure sensors
airFlow
Air flow sensors
vibration
Vibration sensors
all
All of the above numeric sensors
Tip: You can also type the command without adding this
option "all" to get the same data.