Note: If the requested sensor type is not supported, the "Sensor is not available" message is
displayed.
•
•
<option> is one of the options: enable, disable or a numeric value.
Option
enable
disable
A numeric value Sets a value for the specified threshold of a specific inlet sensor
•
•
<hy_value> is a numeric value that is assigned to the hysteresis for the specified inlet sensor.
•
•
<as_value> is a numeric value that is assigned to the assertion timeout for the specified inlet sensor.
Commands for Inlet Pole Sensors
A sensor configuration command for inlet poles begins with sensor inletpole. This type of command is
available on a three-phase PDU only.
You can configure various inlet pole sensor threshold settings at a time by combining multiple
commands.
▶
Set the Upper Critical Threshold for an Inlet Pole:
config:# sensor inletpole <n> <p> <sensor type> upperCritical <option>
▶
Set the Upper Warning Threshold for an Inlet Pole:
config:# sensor inletpole <n> <p> <sensor type> upperWarning <option>
▶
Set the Lower Critical Threshold for an Inlet Pole:
config:# sensor inletpole <n> <p> <sensor type> lowerCritical <option>
▶
Set the Lower Warning Threshold for an Inlet Pole:
config:# sensor inletpole <n> <p> <sensor type> lowerWarning <option>
450
Description
Enables the specified threshold for a specific inlet sensor.
Disables the specified threshold for a specific inlet sensor.
and enables this threshold at the same time.