1) Create a text file containing:
•
• user=<admin_username>
• password=<admin_user_password>
•
•
• destroy_and_format_for_storage=true
2) Save the file as "fwupdate.cfg" on the USB drive.
3) Make sure the Enable Data log backup checkbox is selected in Device Settings > Data Logging.
4) Connect the USB drive to the device.
On the console of the PRO3X, you will see the USB drive is reformatted and existing contents
are removed. Once formatting is done, data is started to be backed up on the USB.
Note: Backed up data on the USB is in encrypted form.
Configuring Data Push Settings
You can push the sensor or asset strip data to a remote server for data synchronization. The destination
and authentication for data push have to be configured properly on the PRO3X.
The data will be sent in JSON format using HTTP POST requests. Each push message contains exactly one
JSON object. The data format is formally defined in IDL files, sharing several definitions from the JSON-
RPC data model. IDL files are available by launching JSON‑RPC online help, which is available on the
Support site for your product.