Note: The SNMP notifications may be SNMP v2c or SNMP v3 traps/informs, depending on the settings for
the System SNMP Notification Action. See Enabling and Configuring SNMP.
Then the SNMP notifications are sent when:
• Any numeric sensor's reading enters the warning or critical range.
• Any sensor reading or state returns to normal.
• Any sensor becomes unavailable.
• The active energy sensor is reset.
• Any state sensor changes its state.
For example, when the outlet 3's voltage exceeds the upper warning threshold, the SNMP
notifications are sent, and when the voltage drops below the upper warning threshold, the
SNMP notifications are sent again.
Sample Inlet-Level Event Rule
In this example, we want the PRO3X to send SNMP notifications to the SNMP manager for any sensor
change event of the Inlet I1.
261