Option
Description
disable
Disables the specified threshold for a specific outlet sensor.
A numeric value Sets a value for the specified threshold of a specific outlet
sensor and enables this threshold at the same time.
<hy_value> is a numeric value that is assigned to the hysteresis for the specified outlet sensor. See
"To De-assert" and Deassertion Hysteresis.
<as_value> is a number in samples that is assigned to the assertion timeout for the specified outlet
sensor. See "To Assert" and Assertion Timeout.
Commands for Outlet Group Sensors
A sensor configuration command for outlets begins with sensor outletgroup.
You can configure various outlet group sensor threshold settings at a time by combining multiple
commands.
Set the Upper Critical threshold for an outlet group sensor:
config:# sensor outletgroup <ID> <sensor type> upperCritical <option>
Set the Upper Warning threshold for an outlet group sensor:
config:#
sensor outletgroup <ID> <sensor type> upperWarning <option>
Set the Lower Critical threshold for an outlet group sensor:
config:# sensor outletgroup <ID> <sensor type> lowerCritical <option>
Set the Lower Warning threshold for an outlet group sensor:
config:#
sensor outletgroup <ID> <sensor type> lowerWarning <option>
Set the deassertion hysteresis for an outlet group sensor:
config:#
sensor outletgroup <ID> <sensor type> hysteresis <hy_value>
447