Variables:
<timing> is the time of the cycling power-off period in seconds, which is an integer between 0 and
3600, or pduDefined for following the PDU-defined timing.
Setting the Inrush Guard Delay Time
This section applies to outlet-switching capable models only.
This command sets the inrush guard delay.
config:#
Variables:
<timing> is a delay time between 100 and 100000 milliseconds.
Setting the Outlet Initialization Delay
This section applies to outlet-switching capable models only.
This command determines the outlet initialization delay timing on device startup. See PDU for
information on outlet initialization delay.
config:#
pdu outletInitializationDelayOnPowerUp <timing>
Variables:
<timing> is a delay time between 1 and 3600 seconds.
Note: This feature does NOT take effect and cannot be configured on a PRO3X device after the outlet
relay is set to the "Latching" mode.
Specifying Non-Critical Outlets
This section applies to outlet-switching capable models only.
This command determines critical and non-critical outlets. It is associated with the load shedding mode.
See Load Shedding Mode.
config:#
pdu nonCriticalOutlets <outlets1>:false;<outlets2>:true
Separate outlet numbers and their settings with a colon. Separate each "false" and "true" setting with a
semicolon.
358
pdu inrushGuardDelay <timing>