Inlet Pole Sensor Threshold Information - LEGRAND Server Technology PRO3X User Manual

Hide thumbs Also See for Server Technology PRO3X:
Table of Contents

Advertisement

Variables:
<n> is the number of the inlet whose sensors you want to query. For a single-inlet PDU, <n> is
always 1.
<sensor type> is one of the following sensor types:
Sensor type
current
voltage
activePower
apparentPower
powerFactor
activeEnergy
unbalancedCurrent
lineFrequency
Displayed information:
Without the parameter "details," only the reading, state, threshold, deassertion hysteresis and
assertion timeout settings of the specified inlet sensor are displayed.
With the parameter "details," more sensor information is displayed, including resolution and range.
If the requested sensor type is not supported, the "Sensor is not available" message is displayed.

Inlet Pole Sensor Threshold Information

This command is only available for a three-phase PDU.
This command syntax shows the specified inlet pole sensor's threshold-related information.
# show sensor inletpole <n> <p> <sensor type>
To show detailed information, add the parameter "details" to the end of the command.
# show sensor inletpole <n> <p> <sensor type> details
Variables:
<n> is the number of the inlet whose pole sensors you want to query. For a single-inlet PDU, <n> is
always 1.
<p> is the label of the inlet pole whose sensors you want to query.
Description
Current sensor
Voltage sensor
Active power sensor
Apparent power sensor
Power factor sensor
Active energy sensor
Unbalanced load sensor
Line frequency sensor