Separate outlet numbers and their delay settings with a colon. Outlets followed by delays are separated
with a semicolon.
Variables:
•
•
<outlet1>, <outlet2>, <outlet3> and the like are individual outlet numbers or a range of outlets
using a dash. For example, 3-8 represents outlets 3 to 8.
•
•
<delay1>, <delay2>, <delay3> and the like are the delay time in seconds.
Note: Power-on sequencing is disabled in the latching mode.
Setting the PDU-Defined Default Outlet State
This section applies to outlet-switching capable models only.
This command determines the initial power condition of all outlets after powering up the PDU. This
setting is used in three scenarios:
•
•
powering up the whole PDU
•
•
powering up a single inlet in a multi-inlet PDU (on most, but not all, multi-inlet units the outlet
boards are powered through the respective inlet)
•
•
transfer switch switches on again after being off due to e.g. internal failure
config:#
pdu outletStateOnPowerUp <option>
Variables:
•
•
<option> is one of the options: off, on or lastKnownState.
Option
Description
off
Switches OFF all outlets when the PRO3X powers up.
on
Switches ON all outlets when the PRO3X powers up.
lastKnownState Restores all outlets to the previous status before powering down
the PRO3X when the PDU powers up again.
Setting the PDU-Defined Cycling Power-Off Period
This section applies to outlet-switching capable models only.
This command sets the power-off period of the power cycling operation for all outlets.
config:#
pdu cyclingPowerOffPeriod <timing>