Field
Description
SSH port
The monitored device's SSH port.
Default is 22.
Power target
Select the outlet or outlet group that is powering the monitored
to switch
device.
Method of
This field determines when PRO3X will power off the outlet(s)
checking
that supplies power to the monitored device, after PRO3X issues
successful
the shutdown command to that device.
shutdown
Timer:
PRO3X will power off the selected outlet or outlet group after
the time specified in the 'Timer delay' field expires.Active
power drop:
PRO3X will power off the selected outlet(s) after
the active power value of the selected outlet or
outlet group drops below the value specified in the
'Active power threshold' field.
Note: Number of available methods is model dependent.
The 'Active power drop' method is available only on models
with outlet metering capability.
Timer delay
This field appears for the 'Timer' method.
Valid values range between 5 and 10,000 seconds.
Active power
threshold
The field appears for the 'Active power drop' method.
Valid values range between 0 and 21,000 W.
Timeout for
shutdown
This field appears for the 'Active power drop' method.
check
Valid values range between 5 and 10,000 seconds.
The power-off operation is performed only when the active power
value of the selected outlet or outlet group drops below the
'Active power threshold' within the period of time specified in this
field.
If the active power value drops below the 'Active power
threshold' after the specified time expires, the power-off
operation will NOT be performed.