5) Click Save.
Power Supply Sensor
The PRO3X's controller receives power from its inlet. A sensor monitors the power supply status and
indicates it on the PDU page.
This status is also available on the PDU's front panel display, or via the CLI with the command: show
pdu details.
State
Description
OK
The controller is receiving power from its own inlet.
fault
The controller cannot receive power from its own inlet because of a
power failure on the inlet or a broken power supply. Instead it is
receiving power from another PRO3X PDU.
See
Power-Sharing Restrictions and Connection
After entering the fault state, this sensor is listed in the Alerted Sensors
section of the Dashboard. .
unavailable The communication with the power supply sensor is lost.
Inlet
You can view all inlet information, configure inlet-related settings, or reset the inlet active energy and
min/max sensor values on the Inlet page. To open this page, click 'Inlet' in the Menu.
(on page 34).