Section 3
SPA operation principle
Figure
3
command function via the configuration logic circuit in a protection IED for control of a circuit
breaker.
A pulse via the binary outputs of the IED normally performs this type of command control. The
SPA addresses to control the outputs OUT1 – OUT16 in SINGLECMD:1 are shown in table 2.
#CD01-CMDOUT1
#CD01-CMDOUT2
#CD01-CMDOUT3
#CD01-CMDOUT4
#CD01-CMDOUT5
#CD01-CMDOUT6
#CD01-CMDOUT7
#CD01-CMDOUT8
#CD01-CMDOUT9
#CD01-CMDOUT10
#CD01-CMDOUT11
#CD01-CMDOUT12
#CD01-CMDOUT13
#CD01-CMDOUT14
#CD01-CMDOUT15
#CD01-CMDOUT16
IEC05000717 V4 EN-US
Figure 3:
The MODE input defines if the output signals from SINGLECMD:1 is off, steady or setable pulse
length signals. This is set in Parameter Setting Tool (PST) under: Main Menu/Settings / IED
Settings / Control / Commands / Single Command or via Parameter Setting Tool (PST).
3.1.2.3

Event function EVENT

The Event function (EVENT) sends time-tagged events to the station level (for example,
operator workplace) over the station bus. On the station level, events are presented in an
event list. Events can be created from both internal logical signals and binary input channels.
All the internal signals are time tagged in the main processing module, while the binary input
channels are time tagged directly on each I/O module. Events are produced according to a set
of event masks. These masks are treated commonly for both LON and SPA channels.
Two special signals for event registration purposes are available in the IED: Terminal Restarted
(0E50) and Event buffer overflow (0E51).
The status and event codes for the EVENT function are found in Table 3.
14
shows an application example of how the user can, in a simplified way, connect the
SINGLECMD
BLOCK
^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
INPUT1
^OUT6
INPUT2
^OUT7
INPUT3
^OUT8
INPUT4
^OUT9
^OUT10
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16
SYNCH OK
Application example showing a simplified logic diagram for control of a
circuit breaker
© Copyright 2017 ABB. All rights reserved
INPUT
AND
OUT
INPUT
NOUT
1MRK 511 396-UEN E
PULSETIMER
OUT
To output board, CLOSE
PULSETIMER
To output board, OPEN
OUT
IEC05000717-4-en.vsd
SPA, 670 series
Communication protocol manual
M11880-82 v6