Section 6
Testing IED operation
ANSI09000643 V1 EN-US
Figure 9:
6.5

Releasing the function to be tested

Release or unblock the function to be tested. This is done to ensure that only the function or the
chain of functions to be tested are in operation and that other functions are prevented from
operating. Release the tested function(s) by setting the corresponding
Function test modes to
When testing a function in this blocking feature, remember that not only the actual function must
be activated, but the whole sequence of interconnected functions (from measuring inputs to
binary output contacts), including logic must be activated. Before starting a new test mode
session, scroll through every function to ensure that only the function to be tested (and the
interconnected ones) have the parameters
respectively. Remember that a function is also blocked if the BLOCK input signal on the
corresponding function block is active, which depends on the configuration. Ensure that the
logical status of the BLOCK input signal is equal to 0 for the function to be tested. Event function
blocks can also be individually blocked to ensure that no events are reported to a remote station
during the test. This is done by setting the parameter
Procedure
40
IA
IB
IC
IN
VA
VB
VC
N
IEC 61850
Connection example of the test equipment to the IED when test equipment is
connected to the transformer input module
No in the local HMI.
Any function is blocked if the corresponding setting in the local HMI under Main
menu/Tests/Function test modes menu remains
Blocked is set to Yes and the parameter TestMode under Main menu/Tests/IED
test mode remains active. All functions that were blocked or released in a previous
test mode session, that is, the parameter
when a new test mode session is started.
© Copyright 2013 ABB. All rights reserved
IA
IB
IC
IN
VA
VB
VC
N
VN
TRIP
ANSI09000643-1-en.vsd
Blocked and eventually EvDisable set to No and Yes
EvDisable to Yes .
Enabled , that is, the parameter
Test mode is set to Enabled , are reset
1MRK 505 289-UUS B
M11413-2 v6
Blocked parameter under
Busbar protection REB650
Commissioning manual