INVT Goodrive350-19 Series Operation Manual page 361

Hide thumbs Also See for Goodrive350-19 Series:
Table of Contents

Advertisement

Goodrive350-19 series VFD for crane
Function
Name
code
DEC position limit
P91.34
mode
Description
voltage*P91.33), output frequency starts
decrease, the regulated target frequency is
(Rated frequency*Present bus voltage/Standard
bus voltage); if the bus voltage increases but it
does not reach the restoration voltage (Standard
bus voltage*(P91.33+5%), the output frequency
remains unchanged; if the bus voltage
continuously decreases, the output frequency
continuously decreases; if the bus voltage rises
and becomes greater than the restoration
voltage, the output frequency increases to the
rated frequency.
P91.32
setting range:
0: Disable
1: Enable
P91.33
setting range: 70.0%–95.0% (Standard
bus voltage 537V)
0–1
0: Single direction limit
1: Bi-directional limit
Upward limit
position
Upward slow
speed area
Upward DEC
position
Downward DEC
position
Downward slow speed
area
Downward limit
position
Single direction limit: When the upward DEC
limit position is reached, the upward slow speed
area is entered, the VFD runs at
stops at sudden if the upward limit position is
reached; the upward speed is restricted, but the
downward speed is not restricted. Downward
-349-
Function parameter list
Default
Load position
measuring
P91.35
and
Modify
0