Goodrive350-19 series VFD for crane
Function
Name
code
Oscillation control
P04.25
threshold of motor
2
P04.26 Energy-saving run
Voltage setting
P04.27
channel
Voltage set
P04.28
through keypad
Voltage increase
P04.29
time
Voltage decrease
P04.30
time
Description
eliminate such phenomenon.
P04.23
setting range: 0–100
P04.24
setting range: 0–100
P04.25
setting range:
output frequency)
0: Disable
1: Automatic energy-saving run
In light-load state, the motor can adjust the
output voltage automatically to achieve energy
saving.
0: Keypad (The output voltage is determined by
P04.28.)
1: AI1
2: AI2
3: AI3
4: HDIA
5: Multi-step speed running (The setting is
determined by group P10.)
6: PID
7: Modbus communication
8: PROFIBUS/CANopen/DeviceNet
communication
9: Ethernet communication
10: HDIB
11: EtherCAT/Profinet communication
12: Programmable expansion card
13: 216 communication
The function code is the voltage digital setting
when "keypad" is selected as the voltage setting
channel.
Setting range: 0.0%–100.0%
Voltage increase time means the time needed
for the VFD to accelerate from min. output
voltage to the max. output frequency.
Voltage decrease time means the time needed
for the VFD to decelerate from the max. output
frequency to min. output voltage.
Setting range: 0.0–3600.0s
-231-
0.00Hz–P00.03
(Max.
Function parameter list
Default
Modify
○
30.00Hz
◎
0
○
0
○
100.0%
○
5.0s
○
5.0s