Do you have a question about the Goodrive100-PV Series and is the answer not in the manual?
Questions and answers
Hamse Ismael
March 9, 2025
I want to connect a low water level sensor to GD100-PV invt how it supposed to do
1 comments:
Mr. Anderson
March 9, 2025
The low water level sensor should be connected to the INVT Goodrive100-PV Series inverter at the designated terminal. Based on the standard wiring diagram:
1. Identify the low water level switch terminals. 2. Connect the common terminal of the sensor to the COM terminal on the inverter. 3. Connect the sensor output to the appropriate input terminal (e.g., S1 or S4) on the inverter. 4. Ensure wiring is secure and correctly configured according to the installation guidelines.
This setup allows the inverter to receive signals from the low water level sensor and respond accordingly.
Goodrive100-PV Series Solar Pump Inverter Contents Contents Contents ............................ i 1 Safety precautions ....................... 1 1.1 Safety definition ......................1 1.2 Warning ......................... 1 1.3 Safety guidelines ......................2 1.3.1 Delivery and installation ..................2 1.3.2 Commissioning and running ................. 3 1.3.3 Maintenance and component replacement ............
Page 3
Goodrive100-PV Series Solar Pump Inverter Contents 5.3 Parameter settings ...................... 20 5.4 Advanced settings ....................... 20 5.4.1 Water discharge speed PI adjustment ..............20 5.4.2 Special settings for single phase motors ............21 6 Function parameter list ...................... 22 6.1 Function parameters related to control ................ 22 P00 group Basic functions ...................
Page 4
D.2 Dimensions of 0.4-2.2kW models ................74 D.3 Dimensions of 1.5-200kW models ................76 Appendix E Further information ..................79 E.1 Product and service quiries ..................79 E.2 Feedback of INVT inverter manuals ................79 E.3 Document library on the Internet ................. 79 -iii-...
Goodrive100-PV Series Solar Pump Inverter Safety precautions 1 Safety precautions Please read this manual carefully and follow all safety precautions before moving, installing, operating and servicing the inverter. If ignored, physical injury or death may occur, or damage may occur to the devices.
Goodrive100-PV Series Solar Pump Inverter Safety precautions 1.3 Safety guidelines Only qualified electricians are allowed to operate on the inverter. Do not carry out any wiring and inspection or changing components when the power supply is applied. Ensure all input power supply is...
Goodrive100-PV Series Solar Pump Inverter Safety precautions PE grounding conductor is the same as that of the phase conductor (with the same cross sectional area). (+) and (-) are DC power supply input terminals. R, S and T (L,N) are AC power supply input terminals.
Goodrive100-PV Series Solar Pump Inverter Safety precautions 1.3.4 Scrap treatment There are heavy metals in the inverter. Deal with it as industrial effluent. When the life cycle ends, the product should enter the recycling system. Dispose of it separately at an appropriate collection point instead of...
Check that there are no signs of water in the package and no signs of damage or breach to the inverter. If not, please contact with local dealers or INVT offices. Check the information on the type designation label on the outside of the package to verify that the name plate is of the correct type.
Goodrive100-PV Series Solar Pump Inverter Product overview Field Description Content Abbreviation Abbreviation ① of product of product GD is short for Goodrive. series series Power range 5R5G—5.5kW ② Rated power + Load type G—Constant torque load 4: AC 3PH 380V (-15%)–440(+10%) 2: AC 3PH 220V (-15%)–240(+10%)
Page 11
Goodrive100-PV Series Solar Pump Inverter Product overview Rated Rated output Rated output Max. DC input Series Model input power current (A) current (A) current (A) (kW) Input/output GD100-1R5G-SS2-PV 15.7 10.2 (0.4-2.2 kW) GD100-2R2G-SS2-PV GD100-0R4G-S2-PV -S2 model GD100-0R7G-S2-PV 0.75 1PH 220V...
Goodrive100-PV Series Solar Pump Inverter Installation guidelines 3 Installation guidelines The chapter describes the mechanical installation and electric installation. Only qualified electricians are allowed to carry out what described in this chapter. Please operate as the instructions in Safety precautions.
Lower than 1000m; When the altitude exceeds 1000m, derate 1% for every increase of 1˚C. Altitude When the altitude exceeds 3000m, consult the local INVT dealer or office. Vibration Max. vibration acceleration: 5.8m/s (0.6g) Installation Install the inverter vertically to ensure good heat dissipation direction performance.
Goodrive100-PV Series Solar Pump Inverter Installation guidelines 3.1.3 Installation mode (1) The inverters ≤ 2.2kW support wall mounting and rail mounting. a) Wall mounting b) Rail mounting Note: The minimum space of A and B is 100mm. H is 36.6mm and W is 35.0mm.
Goodrive100-PV Series Solar Pump Inverter Installation guidelines 3.2 Standard wiring 3.2.1 Main circuit terminals The figure below shows the standard wiring of inverter. PV input Forced switch to mains 1PH/2PH algorithm shifting Common terminal High water level switch GD100-PV Low water level switch...
Page 16
Goodrive100-PV Series Solar Pump Inverter Installation guidelines Terminal Name Function 3PH (1PH) AC input terminals, connected to the grid R, S, T AC input Note: Use the screws equipped with the inverter for (L, N) wiring. (+), (-) PV input...
Goodrive100-PV Series Solar Pump Inverter Installation guidelines U1 and V1 are the common terminals of the windings. Connect them to the output terminal W of the solar pump inverter. Connect U2 to the output terminal U of the inverter. Connect V2 to the output terminal V of the inverter.
Page 18
Goodrive100-PV Series Solar Pump Inverter Installation guidelines Terminal Category Terminal name Terminal function symbol high electrical level corresponds to the single-phase algorithm. A low electrical level corresponds two-phase algorithm. RS485+ 485 communication terminals, using 485 communication RS485- the Modbus protocol...
Goodrive100-PV Series Solar Pump Inverter Keypad operation guidelines 4 Keypad operation guidelines 4.1 Keypad introduction The keypad is used to control the inverter, read inverter status, and set parameters. If you need to install the keypad on another position rather than on the inverter, use a keypad extension cable with a standard RJ45 crystal head.
Page 20
Goodrive100-PV Series Solar Pump Inverter Keypad operation guidelines Item Description Blinking: The inverter is autotuning parameters. On: The inverter is running. Forward or reverse running indicator. FWD/REV Off: The inverter is running forward. On: The inverter is running reversely. Indicates whether the inverter is controlled through the keypad, terminals, or communication.
Goodrive100-PV Series Solar Pump Inverter Keypad operation guidelines Item Description Confirmation Press it to enter menus in cascading mode or DATA confirm the setting of a parameter. UP key Press it to increase data or move upward. DOWN key Press it to decrease data or move downward.
Goodrive100-PV Series Solar Pump Inverter Keypad operation guidelines 4.2.3 Displaying fault information After detecting a fault signal, the inverter enters the fault alarm state immediately, the fault code blinks on the keypad, and the TRIP indicator is on. You can perform fault reset by using the STOP/RST key, control terminals, or communication commands.
Goodrive100-PV Series Solar Pump Inverter Keypad operation guidelines • It cannot be modified in running state and can be modified only in stopped state. Example: Change the value of P00.01 from 0 to 1. DATA The ones place is The ones place is All digits are blinking.
Goodrive100-PV Series Solar Pump Inverter Commissioning guidelines 5 Commissioning guidelines Cut off all power supplies connected to the inverter before terminal wiring, and wait for at least the time designated on the inverter after disconnecting the power supplies. ...
Goodrive100-PV Series Solar Pump Inverter Commissioning guidelines 5.4.2 Special settings for single phase motors a) When the single phase motor is in poor running performance, you can adjust P04 group VF curve settings. Set P04.00=1 and set P04.03–P04.08 to appropriate values according to commissioning conditions.
Goodrive100-PV Series Solar Pump Inverter Function parameter list 6 Function parameter list "○" indicates that the value of the parameter can be modified when the inverter is in stopped or running state. "◎" indicates that the value of the parameter cannot be modified when the inverter is in running state.
Page 27
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code 0: Keypad (LOCAL/REMOT off) The commands are controlled through keypad keys, such as the RUN and STOP/RST keys. The running direction can changed through setting multi-function shortcut key QUICK/JOG to FWD/REV shifting function (P07.02=3).
Page 28
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code frequency if the set frequency is lower than the lower limit. Note: Max. output frequency ≥ Upper limit frequency ≥ Lower limit frequency Setting range: 0.00Hz–P00.04...
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code Do not change the setting of the parameter because reverse running is not allowed in water pump application scenarios. 2: Disable reverse running. It can be used in some special scenarios where reverse running is disallowed.
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code 1: Coast to stop. When a stop command takes effect, the inverter stops output immediately. And the load coasts to stop according to mechanical inertia. Terminal-based...
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code motor configuration of the inverter. If the power of the motor is greatly different from that of the standard motor configuration, the control performance of the...
Page 32
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code 1: Multi-dots V/F curve 2: Torque-down V/F curve (power of 1.3) 3: Torque-down V/F curve (power of 1.7) 4: Torque-down V/F curve (power of 2.0) Curves 2–4 are applicable to the torque loads such as fans and water pumps.
Page 33
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code larger torque boost, however, if the torque boost is too large, the motor will run at over-excitation, which may cause increased output current and motor overheating, thus decreasing the efficiency.
Page 34
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code Setting range of P04.03: 0.00Hz–P04.05 V/F voltage Setting range of P04.04: 0.0%–110.0% ○ P04.06 point 2 of motor 00.0% (rated voltage of motor1) Setting range of P04.05: P04.03–P04.07...
Goodrive100-PV Series Solar Pump Inverter Function parameter list P05 group Input terminals Function Name Description Default Modify code 0: HDI is high-speed pulse input. See ◎ P05.00 HDI input type P05.49–P05.54. 1: HDI is digital input S1 terminals 0: No function ◎...
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code 30: Disable ACC/DEC 31: Counter trigger 32: Reserved 33: Cancel the frequency change setting 34: DC brake 35: Reserved 36: Switch the running command channel to...
Page 37
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code 4: Jogging 5: Inverter in fault 6: Frequency level detection FDT1 7: Frequency level detection FDT2 8: Frequency reached 9: Zero-speed running 10: Upper limit frequency reached...
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code RO1 switch-off ○ P06.11 0.000–50.000s 10.000s delay RO2 switch-on ○ P06.12 0.000–50.000s 0.000s delay RO2 switch-off ○ P06.13 0.000–50.000s 0.000s delay P07 group Human-machine interface Function...
Page 39
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code 0: No function 1: Jogging running. Press QUICK/JOG to begin the jogging running. 2: Switch the display state by the shifting key. Press QUICK/JOG shift displayed function code from right to left.
Page 40
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code 0: Valid only for keypad control 1: Valid both for keypad and terminal control 2: Valid both for keypad and communication control 3: Valid for all control modes...
Page 41
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code 15: Boost module overheat (OH1) Previous 8 fault ● P07.59 16: Inverter module overheat (OH2) type 17: External fault (EF) Previous 9 fault ● P07.60 18: RS485 communication fault (CE)
Goodrive100-PV Series Solar Pump Inverter Function parameter list P08 group Enhanced functions Function Name Description Default Modify code Auto fault reset ○ P08.28 0–10 count Auto fault reset ○ P08.29 0.1–3600.0s 10.0s interval 6.2 Function parameters special for solar pump...
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code can maintain the bus voltage to ensure normal running of the inverter until the recovery of power. Voltage class 220V 400V Frequency decrease 260V 460V point...
Page 44
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code 0.0–100.0% (100.0% corresponds to P15.02) PI adjustment is performed only when the ratio of the difference between the actual PI control voltage and reference voltage to the ○...
Page 45
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code 0.00–100.00 Integral coefficient 2 of the target frequency. ○ P15.09 35.00 A greater value indicates stronger effect and faster adjustment. 0.0–6553.5Vdc If the absolute value of PV voltage minus PI switching ◎...
Page 46
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code and keeps in the state after the delay time P15.14, the system reports A-tF and sleeps. If the delay time is not reached, the signal is bigger than the water level threshold, the time will be cleared automatically.
Page 47
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code 0–10000s Full-water Time setting on full-water level delay. (This ○ P15.14 level delay parameter is still valid for digital full-water signal.) 0–10000s Full-water Time setting on full-water level wake-up ○...
Page 48
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code P15.20, the system reports the underload fault with a delay specified by P15.19. Otherwise, the system runs properly. In the non-continuous situation, the delay counter is automatically cleared.
Page 49
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code undervoltage point or the PV voltage is lower than 70V, the system directly reports the weak-light alarm without any delay. If P15.32=0, in weak-light condition, the system automatically switch to the power-frequency input mode.
Page 50
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code Min. reference voltage in max. power tracking–P15.31 It is the max. voltage tracked when MPPT max. power tracking is valid. The factory value depends on the model.
Page 51
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code P15.27–6553.5V During the max. power tracking, the upper limit of the solar panel reference voltage will Vmppt max. ○ P15.31 not exceed the value of P15.31. The factory 400.0V...
Page 52
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code The pump flow is when the pump Rated pump ○ P15.35 flow runs at the rated frequency and lift. Unit: cubic meter/hour. Rated pump The pump lift is when the pump runs ○...
Goodrive100-PV Series Solar Pump Inverter Function parameter list P17 group Status viewing Function Name Description Default Modify code It is the current of the main winding when Current of the applying capacitance-removing to control ● P17.38 0.0A main winding the single phase motor.
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code with the boost module. Detect that system configured with the boost module. Actual pump ● P18.11 Unit: cubic meter/hour flow ● P18.12 Actual pump lift...
Page 55
Goodrive100-PV Series Solar Pump Inverter Function parameter list Function Name Description Default Modify code This function code is used to set the reference voltage of bus voltage at PV input when the system is configured with Bus reference ◎ P19.06 the boost module.
Goodrive100-PV Series Solar Pump Inverter Fault diagnosis and solution 7 Fault diagnosis and solution Do as follows after the inverter encounters a fault: 1. Check to ensure there is nothing wrong with the keypad. If not, please contact with the local INVT office.
Page 57
Goodrive100-PV Series Solar Pump Inverter Fault diagnosis and solution Fault Fault type Possible cause Solution code circuit or output phase Check whether there is loss. strong interference. There is strong external Check the setting of related interference.
Page 58
Goodrive100-PV Series Solar Pump Inverter Fault diagnosis and solution Fault Fault type Possible cause Solution code SI external fault input Check the external device External fault terminals action. input. The baud rate setting is Set a proper baud rate.
Page 59
Goodrive100-PV Series Solar Pump Inverter Fault diagnosis and solution Fault Fault type Possible cause Solution code running time. inverter reports Check the load and Electronic overload overload pre-alarm overload pre-alarm according to the setting. threshold. To-ground Check whether the motor ...
Page 60
Goodrive100-PV Series Solar Pump Inverter Fault diagnosis and solution Fault Fault type Possible cause Solution code circuit. circuit or line-to-line short circuit) or the rotation is not smooth. The solar cell panel input Reduce the number of solar voltage is too high.
Page 61
Goodrive100-PV Series Solar Pump Inverter Fault diagnosis and solution Fault Fault type Possible cause Solution code check whether terminals are wired correctly. If you have configured the empty-water pre-alarm function, the device Empty-water The pumping pool has automatically stops when...
Goodrive100-PV Series Solar Pump Inverter Options Appendix A Options A.1 Boost module The pump inverters ≤ 2.2KW support the installation of the boost module (PP100-3R2-PV) to improve the utilization of the solar modules. The figure below shows the wiring method.
Figure A–3 Connection between the GPRS module and the inverter For details, see the GPRS/GPS Adaptor Operation Manual which comes with the GPRS module or contact the local INVT office. Provide the model and serial number of the product you query about.
Goodrive100-PV Series Solar Pump Inverter Options A.3 Cable A.3.1 Power cable The sizes of the input power cables and motor cables must comply with local regulations. Note: If the electrical conductivity of the motor cable shield layer does not meet the requirements, a separate PE conductor must be used.
50 m, an output reactor must be added on the output side of the inverter. If the distance between the inverter and motor is 50 m to 100 m, select the reactor according to the following table. If the distance is longer than 100 m, contact INVT's technical support technicians.
A.5 Filter Goodrive100-PV series inverters of ≥ 4kW contain built-in C3 filters. You can use the jumper J10 to determine whether to connect it. Connection method: Open the lower cover, find the location of J10, and insert the jumper terminals delivered with the inverter.
Goodrive100-PV Series Solar Pump Inverter Recommended solar module configuration Appendix B Recommended solar module configuration B.1 Recommended solar module configuration for solar pump inverters Open-circuit voltage class of solar module 37± 1V 45± 1V Solar pump inverter model Modules per...
Goodrive100-PV Series Solar Pump Inverter Recommended solar module configuration Open-circuit voltage class of solar module 37± 1V 45± 1V Solar pump inverter model Modules per Modules per Module power Module power string * string * ± 5Wp ± 5Wp Strings...
Goodrive100-PV Series Solar Pump Inverter Power frequency & PV switching solution Appendix C Power frequency & PV switching solution C.1 Solution introduction Generally, inverters do not allow simultaneous connection of power frequency and PV. If such simultaneous connection is required, switching control circuit needs to be configured externally.
Page 71
Goodrive100-PV Series Solar Pump Inverter Power frequency & PV switching solution Field Sign Description Content 055A—applies to inverters of ≤ 15kW Rated Power range for ② 110A—applies to inverters of 18.5– current adaptive inverter 37kW Voltage 4: AC 3PH 380V (-15%)–440 (+10%) ③...
1000VDC 1600V C.2 IP54 protection-level inverters INVT provides IP54 protection-level inverters, which are divided into two types: One type implements auto power frequency & PV switching and the other type does not implement auto switching. The following figure shows the dimensions of the inverter.
Page 74
Goodrive100-PV Series Solar Pump Inverter Power frequency & PV switching solution Dimensions of IP54 inverter (unit: mm): Power (kW) Model GD100-037G-45-PV-AS GD100-030G-45-PV-AS 1000 GD100-022G-45-PV-AS 18.5 GD100-018G-45-PV-AS GD100-015G-45-PV-AS GD100-011G-45-PV-AS GD100-7R5G-45-PV-AS GD100-7R5G-25-PV-AS GD100-5R5G-45-PV-AS GD100-5R5G-25-PV-AS GD100-004G-45-PV-AS GD100-004G-25-PV-AS GD100-2R2G-45-PV-AS GD100-2R2G-S25-PV-AS GD100-2R2G-SS25-PV-AS GD100-1R5G-45-PV-AS GD100-1R5G-S25-PV-AS GD100-1R5G-SS25-PV-AS GD100-0R7G-45-PV-AS 0.75...
Goodrive100-PV Series Solar Pump Inverter Power frequency & PV switching solution cannot be greater than 440V. For -45 models equipped with the boost module, the DC input voltage cannot be greater than 600V. C.3 Wiring description The following figures show the wiring terminals of IP54 inverters.
Goodrive100-PV Series Solar Pump Inverter Power frequency & PV switching solution Terminal Symbol Description name L, N AC input 1PH 220V AC input terminals, connected to the grid (+), (-) PV DC input Input terminals of photovoltaic panels. 3PH/1PH AC output terminals, connected to pump motor.
Goodrive100-PV Series Solar Pump Inverter Dimension drawings Appendix D Dimension drawings D.1 External keypad structure Keypad structure Installation hole Note: The inverter models of 380V 2.2kW and lower support an optional extermal keypad, and the keypad of inverter models of 380V 4kW and higher can be installed on another device.
Further information Appendix E Further information E.1 Product and service quiries If you have any queries about the product, contact the local INVT office. Please provide the model and serial number of the product you query about. You can visit www.invt.com to find a list of INVT offices.
Need help?
Do you have a question about the Goodrive100-PV Series and is the answer not in the manual?
Questions and answers
I want to connect a low water level sensor to GD100-PV invt how it supposed to do
The low water level sensor should be connected to the INVT Goodrive100-PV Series inverter at the designated terminal. Based on the standard wiring diagram:
1. Identify the low water level switch terminals.
2. Connect the common terminal of the sensor to the COM terminal on the inverter.
3. Connect the sensor output to the appropriate input terminal (e.g., S1 or S4) on the inverter.
4. Ensure wiring is secure and correctly configured according to the installation guidelines.
This setup allows the inverter to receive signals from the low water level sensor and respond accordingly.
This answer is automatically generated