Goodrive350-19 series VFD for crane
Function
Name
code
Frequency drop at
P11.01
transient
power-off
Enabling
energy-consumpti
P11.02
on braking for
stop
Overvoltage
P11.03
stalling protection
Overvoltage
P11.04
stalling protection
voltage
P11.05 Current limit mode
Description
fault occurs, it reports SPI.
1: During stop, if a hardware input phase loss
fault occurs, it reports A-SPI.
0: Disable
1: Enable
0: Enable
1: Disable
0: Disable
1: Enable
DC bus voltage V
Overvoltage stall
threshold
Output
frequency
Note: It can be modified only when
indicating special functions are enabled.
120–150% (standard bus voltage) (380V)
120–150% (standard bus voltage) (220V)
During accelerated running, as the load is too
large, the actual acceleration rate of motor is
lower than that of output frequency, if no
measures are taken, the VFD may trip due to
overcurrent during acceleration.
0x00–0x21
Ones place: Hardware and software current-limit
action selection
0: Invalid
1: Always valid
Tens: Hardware current limit overload alarm
selection
-273-
Function parameter list
Default
0
0
0
Time t
Time t
P11.26
is 1
136%
120%
10
Modify
○
◎
○
○
◎