Goodrive350-19 series VFD for crane
Function
code
corresponding to lower
P06.19
AO1 output upper limit
P06.20
corresponding to upper
P06.21
AO1 output filter time
Slave parameters:
Function
code
P03.11
Torque setting method 2: AI1
P03.32
Enabling torque control 1: Enable
P05.24
AI1 lower limit
Corresponding setting
P05.25
of AI1 lower limit
P05.26
AI1 upper limit
Corresponding setting
P05.27
of AI1 upper limit
P05.28
AI1 input filter time
Note: When the terminal master/slave function is used, commissioning is unrelated to P28.
5.14.3 Master/slave communication
The VFDs can implement the master/slave control function by using the CAN master/slave
communication card. The wiring diagram is as follows.
Master
CAN
master/slave
communication
card
The specific CAN communication master/slave modes are: master/slave mode 0–2 are master/slave
power balance modes, master/slave mode 4 is the master/slave speed synchronization mode, and
master/slave mode 3 is reserved. Master/slave mode 0 and master/slave mode 1 are used often.
Name
P06.19
limit
P06.20
P06.21
AO1 output
limit
Name
P05.24
P05.25
P05.26
P05.27
P05.28
VFD
CANH
CANL
Description
setting range: P06.17–100.0%
setting range: 0.00V–10.00V
setting range: 0.000s–10.000s
Description
setting range:
0.00V–P05.26
setting range: -300.0% –300.0%
setting range: P05.24–10.00V
setting range: -300.0% –300.0%
setting range: 0.000s–10.000s
-100-
Commissioning guidelines
Slave
VFD
CAN
CANH
master/slave
communication
CANL
card
Setting
100.0%
10.00V
0.000s
Setting
2
1
0.00V
0.0%
10.00V
100.0%
0.030s