Goodrive350-19 series VFD for crane
Function
Name
code
decimal points of
frequency
Number of
P08.24
decimal points of
linear speed
P08.25 Set counting value P08.26–65535
Designated
P08.26
counting value
P08.27
Set running time 0–65535min
Auto fault reset
P08.28
count
Auto fault reset
P08.29
interval
Frequency
P08.30
decrease ratio in
drop control
Channel for
switching between
P08.31
motor 1 and motor
2
Description
1: One
0: No decimal point
1: One
2: Two
3: Three
0–P08.25
Auto fault reset count: When the VFD uses
automatic fault reset, it is used to set the number
of automatic fault reset times. When the number
of continuous reset times exceeds the value, the
VFD reports a fault and stops.
Auto fault reset interval: Time interval from when
a fault occurred to when automatic fault reset
takes effect.
After VFD starts, If no fault occurred within 600s
after the VFD starts, the number of automatic
fault reset times is cleared.
setting range: 0–10
P08.28
P08.29
setting range: 0.1–3600.0s
The output frequency of the VFD changes as the
load changes. The function code is mainly used
to balance the power when several motors drive
a same load.
Setting range: 0.00–50.00Hz
0x00–0x14
Ones place: Switchover channel
0: Terminal
1: Modbus communication
2: PROFIBUS/CANopen/DeviceNet
communication
3: Ethernet communication
4: EtherCAT/Profinet communication
5: 216 communication
-259-
Function parameter list
Default
Modify
○
0
○
0
○
0
○
0min
○
0
○
1.0s
○
0.00Hz
◎
0x00