Goodrive350-19 series VFD for crane
Function
Name
code
Wake-up-from-sle
P01.20
ep delay
Power-off restart
P01.21
selection
Wait time for
P01.22
restart after
power-off
P01.23
Start delay
Description
Used to set the wake-up-from-sleep delay time.
When the running frequency of the VFD is lower
than the lower limit, the VFD becomes standby.
When the set frequency exceeds the lower limit
one again and it lasts for the time set by P01.20,
the VFD runs automatically.
t1 < P01.20, the VFD does not run
Frequency f
t1+t2 ≥P01.20, the VFD runs
t0=P01.34, sleep delay
Frequency lower
limit f0
t0
Run
Coast to
stop
Setting range: 0.0–3600.0s (Valid only when
P01.19=2)
Indicates whether the VFD automatically runs
after re-power on.
0: Disable
1: Enable. If the restart condition is met, the VFD
runs automatically with the wait time P01.22.
Indicates the wait time before the automatic
running of the VFD that is re-powered on.
Output frequency
Running
Power off
Setting range: 0.0–3600.0s (Valid only when
P01.21=1)
After a VFD running command is given, the VFD
is in standby state and restarts with the delay
defined by
P01.23
to implement brake release.
Setting range: 0.0–600.0s
-215-
Set frequency curve:
Running frequency curve:
t2
t1
Sleep
Run
t1=P01.22
t2=P01.23
t1
t2
Running
Power on
Function parameter list
Default
Modify
0.0s
Time t
0
1.0s
t
0.0s
○
○
○
○