5.4.6 Controlling the vortex module through the AO terminal

R
S
T
Note: Turn SW2 on the control board to "V" for voltage output.
Controlling the vortex module through the AO terminal
1. Connect the AO terminal to the vortex module according to the figure.
2. Set P06.14=0 to select running frequency output for AO1.
3. Set P06.17–P06.21 to adjust the vortex module output voltage percentage.
The output voltage percentage is the ratio of running frequency to P00.03.
Function code settings:
Function
code
P06.14
P06.17
AO1 output lower limit
AO1 output corresponding to
P06.18
P06.19
AO1 output upper limit
AO1 output corresponding to
P06.20
P06.21
AO1 output filter time
Braking resistor
(+)
R
S
T
I
V
Figure 5-6 Connecting the AO terminal to the vortex module
Name
AO1 output
lower limit
upper limit
PB
U
V
W
VFD
AO
Vortex module
COM
Description
0: Running frequency
-300.0%–P06.19
0.00V–10.00V
P06.17–100.0%
0.00V–10.00V
0.000s–10.000s
-52-
Commissioning guidelines
M
3~
M
3~
Default
0
16.0%
2.00V
60.0%
10.00V
0.000s