Goodrive350-19 series VFD for crane
P92 group––Hoisting protection function group 3
Function
Name
code
Enabling low
P92.00
voltage protection
Low voltage
P92.01
protection point
Low-speed run
P92.02
protection time
Setting of
P92.03
low-speed run
frequency
Description
Output
frequency
Brake
frequency
Bus voltage
Normal bus voltage
P92.01*Motor rated
voltage+20V
P92.01*Motor rated
voltage
Running
command
Low voltage
protection
output
VFD
status
When P92.00=1, if the bus voltage is less than
(P92.01*Motor rated voltage), low voltage
protection is started, the VFD decelerates to
stop.
If the bus voltage restores to a value greater
than (P92.01*Motor rated voltage + 20V), low
voltage protection is automatically disabled.
P92.00
setting range:
0: Disable
1: Enable
P92.01
setting range: 1.00–1.30
Low-speed run protection is applied to devices
to which long-time low speed running is not
applicable, preventing overheating caused by
late dissipation.
Output
frequency
(Hz)
P92.03
Running
command
Low speed
protection
output
When
P92.02
is a non-zero value, low-speed
running protection is enabled, if the running
frequency of the VFD is equal to or less than
-353-
Time
Time
A-LvP
Time (s)
P92.02
Function parameter list
Default
Modify
◎
0
○
1.05
◎
0.000s
○
5.00Hz