E Codes (Extension Terminal Functions) - Fuji Electric FRENIC-HVAC User Manual

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

6.3.2

E codes (Extension terminal functions)

E01 to E07
Terminal [X1] to [X7] Functions
E01 to E07, E98 and E99 assign commands (listed below) to general-purpose, programmable,
digital input terminals, [X1] to [X7], [FWD], and [REV].
These function codes can also switch the logic system between normal and negative to define
how the inverter logic interprets the ON or OFF state of each terminal. The factory default
setting is normal logic system "Active ON." So, descriptions that follow are given in normal
logic system. They are, in principle, arranged in the numerical order of assigned data.
However, highly relevant signals are collectively described where one of them first appears.
Refer to the function codes in the "Related function codes" column, if any.
• Ensure safety before modifying the function code settings.
Run commands (e.g., "Run forward" FWD and "Fire mode" FMS), stop commands (e.g.,
"Coast to a stop" BX), and frequency change commands can be assigned to digital input
terminals. Depending upon the assignment states of those terminals, modifying the function
code setting may cause a sudden motor start or an abrupt change in speed.
• When the inverter is controlled with the digital input signals, switching run or frequency
command sources with the related terminal commands (e.g., SS1, SS2, SS4, SS8, Hz2/Hz1,
Hz/PID, IVS, LE and FMS) may cause a sudden motor start or an abrupt change in speed.
An accident or physical injury may result.
Function code data
Active
ON
0
1
2
3
4
5
6
7
8
1009
11
13
14
15
16
17
18
19
20
Terminal commands assigned
Active
OFF
1000
1001
Select multistep frequency
(0 to 15 steps)
1002
1003
1004
Select ACC/DEC time (2 steps)
1005
Select ACC/DEC time (4 steps)
1006
Enable 3-wire operation
1007
Coast to a stop
1008
Reset alarm
9
Enable external alarm trip
1011
Select frequency command 2/1
Enable DC braking
1014
Select torque limiter level 2/1
Switch to commercial power (50 Hz)
Switch to commercial power (60 Hz)
1017
UP (Increase output frequency)
1018
DOWN (Decrease output frequency)
1019
Enable data change with keypad
1020
Cancel PID control
6-84
E98 and E99 (Terminal [FWD] and [REV] Functions)
SS1
SS2
SS4
SS8
RT1
RT2
HLD
BX
RST
THR
Hz2/Hz1
DCBRK
TL2/TL1
SW50
SW60
UP
DOWN
WE-KP
Hz/PID
Related
Symbol
function
codes
C05 to C19
F07, F08,
E10 to E15
F02
F01, C30
F20 to F22
F40, F41, E16,
E17
Frequency
setting:
F01, C30
PID command:
J101, J201
F00
J101 to J131
J201 to J231

Hide quick links: