The following tables list the function codes available for the FRENIC-HVAC series of inverters.
F codes: Fundamental Functions
Code
Name
F00
Data Protection
F01
Frequency Command 1
F02
Operation Method
F03
Maximum Frequency 1
F04
Base Frequency 1
F05
Rated Voltage at Base Frequency 1
F06
Maximum Output Voltage 1
F07
Acceleration Time 1
F08
Deceleration Time 1
F09
Torque Boost 1
F10
Electronic Thermal Overload Protection for
Motor 1
(Select motor characteristics)
F11
(Overload detection level) OFF: Disable
F12
(Thermal time constant) 0.5 to 75.0 min
F14
Restart Mode after Momentary Power
Failure
(Mode selection)
F15
Frequency Limiter
F16
F18
Bias
(Frequency command 1) -100.00% to 100.00%
F20
DC Braking 1
(Braking starting frequency)
F21
(Braking level) 0% to 60%
F22
(Braking time) OFF (Disable); 0.01 to 30.00 s
F23
Starting Frequency 1
F24
(Holding time) 0.00 to 10.00 s
F25
Stop Frequency
The shaded function codes (
) are applicable to the quick setup.
*2 The motor rated current is automatically set. See Table B (function code P03).
*3 5.0 min for inverters of 30 HP or below; 10.0 min for those of 40 HP or above.
Data setting range
0: Disable both data protection and digital reference protection
1: Enable data protection and disable digital reference protection
2: Disable data protection and enable digital reference protection
3: Enable both data protection and digital reference protection
0:
/
/
/
keys on keypad
1: Voltage input to terminal [12] (-10 to +10 VDC)
2: Current input to terminal [C1] (4 to 20 mA DC)
3: Sum of voltage and current inputs to terminals [12] and [C1]
5: Voltage input to terminal [V2] (0 to 10 VDC)
7: Terminal command UP/DOWN control
8:
/
/
/
keys on keypad
(balanceless-bumpless switching available)
10: Pattern operation
0: FWD/REV/STOP keys on keypad (Motor rotational direction
specified by terminal command FWD/REV)
1: External signals (Terminal command FWD or REV )
2: FWD/STOP keys on keypad (forward)
3: REV/STOP keys on keypad (reverse)
25.0 to 120.0 Hz
25.0 to 120.0 Hz
OFF: Disable AVR (Output a voltage in proportion to input voltage)
80-240 V: Output an AVR-controlled voltage (230 V class series)
160-500 V: Output an AVR-controlled voltage (460 V class series)
200-600 V: Output an AVR-controlled voltage (575 V class series)
80-240 V: Output an AVR-controlled voltage (230 V class series)
160-500 V: Output an AVR-controlled voltage (460 V class series)
200-600 V: Output an AVR-controlled voltage (575 V class series)
0.00 to 3600.00 s
Note: Entering 0.00 cancels the acceleration time, requiring
external soft-start.
0.0% to 20.0% (percentage with respect to "F05: Rated Voltage at
Base Frequency 1")
1: For a general-purpose motor with shaft-driven cooling fan
2: For an inverter-driven motor, non-ventilated motor, or motor
with separately powered cooling fan
1% to 135% of the inverter rated current
0: Trip immediately
1: Trip after a recovery from power failure
3: Continue to run, for heavy inertia or general loads
4: Restart at the frequency at which the power failure occurred,
for general loads
5: Restart at the starting frequency
(High) 0.0 to 120.0 Hz
(Low) 0.0 to 120.0 Hz
0.0 to 60.0 Hz
on the basis of inverter rated current
0.1 to 60.0 Hz
0.1 to 60.0 Hz
6-3
6.2 Function Code Tables
Change
Data
Default
Related
when
copying
setting
page
running
Y
Y
0
6-41
N
Y
0
6-42
N
Y
0
6-49
N
Y
60.0
6-50
60.0
N
Y
N
Y
230
460
575
N
Y
Y
Y
20.00
6-53
Y
Y
20.00
Y
Y
0.0
6-55
Y
Y
1
Y
Y1
*2
Y
Y
*3
Y
Y
0
6-59
Y
Y
70.0
6-66
Y
Y
0.0
Y*
Y
0.00
6-67
Y
Y
0.0
Y
Y
0
Y
Y
OFF
Y
Y
0.5
6-69
Y
Y
0.00
Y
Y
0.2