Display Attached Controller @E.Terminal for MC USER'S MANUAL Hardware FEH300b...
Page 2
This hardware edition of the user’s manual describes system composition, specifications, and handling of the @E.Terminal. In order to operate the hardware properly, please read this user’s manual carefully. When using modules or peripheral devices, be sure to read the corresponding user’s manuals listed below. Title @E.Terminal for MC User's Manual <Function>...
Be sure to read the “Safety Precautions” thoroughly before using the module. Here, the safety precaution items are classified into “Warning” and “Caution.” Warning Incorrect handling of the device may result in death or serious injury. Caution Incorrect handling of the device may result in minor injury or physical damage. Even some items indicated by “Caution”...
Page 4
Safety Precautions Check the appearance of the unit when it is unpacked. Do not use the unit if any damage or deformation is found. Failure to do so may lead to fire, damage or malfunction. For use in a facility or for a system related to nuclear energy, aerospace, medical, traffic equipment, or mobile installations, please consult your local distributor.
Page 5
[General Notes] • Never bundle control cables nor input/output cables with high-voltage and large-current carrying cables such as power supply cables. Keep these cables at least 200 mm away from the high-voltage and large-current carrying cables. Otherwise, malfunction may occur due to noise. •...
Page 6
• Display part is changed from UG40 series to V8 series. • Accessory "Noise filter" is eliminated from controller hardware version "03" or later. Dec. 2008 FEH300b @E.Terminal (No contents installed) was added. Revisions *Manual No. is shown on the cover.
The @E.Terminal for MC Display Attached Controller is an all-in-one programmable operation display and motion controller. Features: 1) The guidance function of the display screen allows you to easily set up parameters and positioning data previously set up by a dedicated machine. Also, it enables easy equipment maintenance.
1-2 Appearance @E.Terminal for MC is composed of a programmable operation display (the display unit) and a controller unit attached to the back of the display unit. The controller unit is attached with screws to the connector area of the communication unit at the back of the display unit, similar to the way in which the communication unit is attached.
Page 12
1-3 Types • Auxiliaries and others Names Types Battery for display unit V7-BT Replacement backlight for V812-FL V810-FL V808S-FL Battery for controller NP8P-BT SX bus terminating plug NP8B-BP SX bus expansion cabl NP1C-P3 NP1C-P6 NP1C-P8 NP1C-02 NP1C-05 NP1C-10 NP1C-15 NP1C-25 * For information about peripheral accessories of the display unit not documented in this manual, please refer to “V8 series Hardware Specifications (2016NEx)”.
The following illustration shows the system composition of @E.Terminal for MC. USB-B MJ1/MJ2 "V-CP" Screen editor "V-SFT-5" @E.Terminal for MC (V5.3.0.0 or later) "NW0H-CNV + NW0H-CA3" commercially available USB cable Programming support tool SX-Programmer Standard "NP4H-SWN" (V2.3.5.1 or later) SX-Programmer Expert (D300win) "NP4H-SEDBV3"...
2-1 Specifications 2-1-2 Display unit specifications (1) Display unit specifications Item Display device Display size Colors Display resolution (W x H) Dot pitch (W x H) Backlight Backlight life (average life of backlight only) Backlight auto OFF function Brightness adjustment Surface sheet material POWER lamp (2) Touch switch specifications...
2-1 Specifications (6) Drawing environment Item Specifications Drawing method Exclusive configuration software Drawing tool Name of exclusive configuration software: V-SFT-5 Personal computer: Pentium III 800 MHz or above Capacity of hard disk required: Display: (7) Display function specifications Item Specifications Interface language (Note: 1) Japanese...
Page 19
(8) Function performance specifications Item Specifications Screens Max. 1024 Screen memory Flash memory: Approx. 12.5 Mbytes (Varies depending on the font) Switch 1024 per screen Switch actions Set, reset, momentary, alternate, to light (Possible to press a function switch and a switch on the display at the same time) Lamp Reverse, blink, exchange of graphics 1024 per screen...
2-1 Specifications 2-1-3 Controller unit specifications (1) Application performance specifications Item Type Control system Input / Output connection method I/O control system Memory types Programming language Program memory capacity Memory I/O memory General memory Retain memory User FB instance memory Memory for System FB Timer...
(2) Specific system memory The table below lists system memory specific to @E.Terminal controller unit. [Expansion annunciator relay area] Address Names Display unit connection status SM1240 flag (%MX10.124.0) [Cause of memory error] Address Names SM84 Display unit DPRAM error (%MX10.8.4) 2-1 Specifications Descriptions Represents whether a display unit is connected...
2-2 Dimensions and Panel Cut-out 2-2-1 External dimensions and panel cut-out dimensions for the NP5M0101-5H4/NP5N0011-5H4 • Front view 326.4 SYSTEM • Rear view 312.0 SX-BUS UROM 4:RUN 3:U-TERM 2:TERM 1:STOP 24V DC USER ROM CARD • Bottom view 312.0 • Side view (66) Note) LOADER...
2-2-2 External dimensions and panel cut-out dimensions for the NP5M0101-4H4/NP5N0011-4H4 • Front view 303.8 • Rear view 288.0 SX-BUS UROM 4:RUN 3:U-TERM 2:TERM 1:STOP 24V DC USER ROM CARD • Bottom view 288.0 2-2 Dimensions and Panel Cut-out SYSTEM • Side view (66) Note) LOADER...
2-3 Names and Functions (3) NP5M0101-3H4/NP5N0011-3H4 1) Display This is the display unit. 2) Power lamp (POWER) Illuminates in green when the display unit is powered on, and is operating normally. Flashes when an error occurs to the backlight (burned-out backlight, etc.). 3) Function keys Used for RUN/STOP selection, brightness adjustment and backlight ON/OFF (setting on the V-SFT-5 editor required).
Page 27
2-3 Names and Functions 9) Power supply terminal block (display unit) Supplies the power to the display unit (24 V DC). 10) Modular jack 1 (MJ1) Used for screen data transfer and connection with PLCs or other peripheral devices. 11) Modular jack 2 (MJ2) Used for connection with PLCs or other peripheral devices.
2-3 Names and Functions 2-3-2 Controller unit 1) Status indication SX-BUS 5) SX bus connector Power supply terminal block (3 poles) 24V DC Version No. Name plate Seal of the occasion of next battery replacement 2) Key switch UROM 3) CPU No. selection key switch 4:RUN 3:U-TERM 2:TERM...
Page 29
1) Status indication LED (Controller unit) Symbol Color Descriptions Green Status of the controller unit. <Lights on pattern> Blinks - UROM Green Lights on continuously when the CPU recognizes a user ROM card. Lights on continuously when a user ROM card (compact flash card) is correctly installed in the CPU module and the key switch is set to "3"...
2-4 Serial Connector Communication (RS-232C, RS-422/485) with a controller is enabled via the serial connector (CN1). • For NP5M0101-5H4/4H4 NP5N0011-5H4/4H4 Bottom view The serial connector pins correspond to signals as given below. CN1 (D-sub 9-pin, female) RS-232C (Note: 1) Pin No. Signal Contents Not used...
A screen data transfer cable (MJ1 only), temperature controller, barcode reader, CREC, or V-I/O can be connected to the modular jack (MJ1 or MJ2). • For NP5M0101-5H4/4H4 NP5N0011-5H4/4H4 Bottom view Pins of MJ1 and MJ2 correspond to signals as given below. MJ1/2 Note: 1) Allowable current for the external power supply +5V at MJ1/MJ2/USB-A of the @E.Terminal.
2-6 Dip Switches In NP5M0101-5H4/4H4, NP5N0011-5H4/4H4, the dip switch is hidden by the controller unit. Operate the dip switch by detaching the controller unit. The @E.Terminal is equipped with eight (1 to 8) dip switches. When setting the dip switch, turn the power off. Upon delivery, all the dip switches are set to OFF.
Page 33
Dip switch number 2 (CF Card interface cover access control) When the dip switch number 2 is set to the ON position, access to the CF card is possible whether the cover is opened or not. In case access to the CF card is disabled because of Caution damage of the CF card interface cover, set the dip switch number 2 to the ON position.
(1) Mounting procedure 1) Insert the @E.Terminal unit into the mounting panel (max. thick: 5 mm). 2) Insert four fixtures attached to the @E.Terminal unit into the mounting holes, and tighten them with the tightening screws. Tightening torque: 0.5 to 0.7 N·m Fixture dimensions (Unit: mm) 10.5...
3-2 Power Supply Cable Wiring Electric shock hazard. Warning Shut the power off before wiring the power supply cable. (1) Power supply cable wiring Power supply terminal blocks of the display unit and the controller unit are connected with each other with a cable by default.
Page 37
• Tighten terminal screws on the power supply terminal block of the display unit with the following torque. Use a power supply cable within the range shown below. Types Screw Tightening size torque NP5M0101-5H4 NP5M0101-4H4 M3.5 0.8N· m NP5N0011-5H4 NP5N0011-4H4 NP5M0101-3H4 M3.5 1.2N·...
Page 38
3-2 Power Supply Cable Wiring (2) Grounding Be sure to establish a ground of the @E.Terminal. Caution (The level of grounding resistance should be less than 100 .) • An independent earth pole must be used for the @E.Terminal. • Use a cable which has a nominal cross section of more than 2 mm •...
Section 4 Inspection and Maintenance Be sure to turn off the power before conducting inspection or maintenance. Warning Failure to do so could cause an electric shock or damage to the unit. 4-1-1 Daily inspection • Check that the screws on the @E.Terminal are tightened firmly. •...
4-2 Battery Replacement When the time comes to replacement the battery, replace it for a new one even if battery error is not displayed. Also, when low battery voltage of the display unit and the controller unit is discovered, replace the battery for a new one immediately.
Page 42
Battery replacement • Battery replacement of display unit 1) Remove the controller unit from @E.Terminal. Remove mounting screws at three places to remove the controller unit from the display unit. Be careful not to drop or lose the mounting screws. Mounting screws at three places M3 screws thread, Tightening torque:...
4-3 Maintenance Services 4-3-1 Ordering notes When ordering electrical and control equipment (or requesting price estimates), the following general notes are to be observed, unless otherwise specified in the estimation paper, contract paper, catalogs, or specifications. When the product is delivered, check the contents of the package as soon as possible. Even before inspection, use caution on storing and using the product safely.
Appendix 1 About Project for @E.Terminal (No contents installed) Page Appendix 1 About Project for @E.Terminal (No contents installed) ... App. 1-1...
Page 45
Appendix 1 About Project for @E.Terminal (No contents installed) When you make new project for controller of @E.Terminal (No contents installed) by personal computer loader (SX- programmer Expert/ Standard), download template for new project from our homepage. The project for controller of @E. Terminal for MC is stored in backup CD. (1) Download template Access to our homepage, download from [Software libraries] of [Programmable controllers].
Page 46
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032,Japan Phone: +81-3-5435-7280 Fax: +81-3-5435-7425 http://www.fesys.co.jp/eng/ Printed on recycled paper. Printed in Japan 2008-12 FIS...