Function Code Basic Settings < 1 - Fuji Electric FRENIC-HVAC User Manual

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

 Dynamic torque vector control
To get the maximal torque out of a motor, this control calculates the motor torque for the load
applied and uses it to optimize the voltage and current vector output.
Selecting this control automatically enables the auto torque boost and slip compensation function.
This control is effective for improving the system response to external disturbances such as load
fluctuations, and the motor speed control accuracy.
5.7.8
Function code basic settings < 1 >
Driving a Fuji general-purpose motor under the V/f control (F42 = 0 or 2) or dynamic torque vector
control (F42 = 1) requires configuring the following basic function codes.
Select any of the Fuji standard 8-series, HP motor typical model and others with the function code
P99.
Configure the function codes listed below according to the motor ratings and your machinery design
values. For the motor ratings, check the ratings printed on the motor's nameplate. For your
machinery design values, ask system designers about them.
For details on how to modify the function code data, see Section 5.6.3.1 "Setting up function
codes."
Function
Name
code
F04
Base frequency 1
Rated voltage at base
F05
frequency 1
P99
Motor 1 selection
Motor 1
P02
(Rated capacity)
F03
Maximum frequency 1
Acceleration time 1
F07
(Note)
Deceleration time 1
F08
(Note)
Function code data
Motor ratings
(printed on the nameplate of the motor)
0: Motor characteristics 0
(Fuji standard motors, 8-series)
1: Motor characteristics 1
(HP rating motors)
4: Other motors
Capacity of motor connected
Machinery design values
(Note) For a test-driving of the motor,
increase values so that they are longer than
your machinery design values. If the specified
time is short, the inverter may not run the
motor properly.
5-101
5.7 Alarm Mode
Factory default
60.0 (Hz)
230/460/575 V class series
230/460/575 (V)
1 (HP rating motors)
Nominal applied motor
capacity
60.0 (Hz)
20.00 (s)
20.00 (s)