Configuration sample 3: One-shot operation
When starting the inverter by short-circuiting the SW-FWD or SW-REV switch and stopping
it by short-circuiting the SW-STOP switch (which are functionally equivalent to depression
of the
key or
key on the keypad, respectively), using a customizable logic instead of
/
a conventional external circuit simplifies the external circuit as shown below.
To configure the above customizable logic, set function codes as listed below. The "Type of
timer" and "Time setting" require no modification unless otherwise specified.
Function Code
E01 Terminal [X1] Function
E98 Terminal [FWD] Function
E99 Terminal [REV] Function
U00 Customizable Logic (Mode selection)
U01 Customizable Logic:
Step 1
U02
U03
U06 Customizable Logic:
Step 2
U07
U08
Setting
Data
100
No function assigned,
NONE
100
No function assigned,
NONE
100
No function assigned,
NONE
1
Enable
(Logic circuit)
3
ORing +
General-purpose timer
(Input 1)
4011
Terminal [REV] input
signal, REV
(Input 2)
4001
Terminal [X1] input
signal, X1
(Logic circuit)
6
Reset priority flip-flop
+ General-purpose
timer
(Input 1)
4010
Terminal [FWD] input
signal, FWD
(Input 2)
2001
Output of step 1, SO01