Fuji Electric FRENIC-HVAC User Manual page 443

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

Example: To detect 0 to 30 kPa with 1 to 5 V output of the pressure sensor
1) Input monitor
Set E61 (Terminal [12] extended function) to "20."
2) Gain
To interpret 5V as 100%, set the gain to 200% (C32 = 100%, C34 = 50%).
3) Scale
- Maximum scale (C59): Set 30.0 to be displayed when the analog input value on
terminal [12] is 100%.
- Minimum scale (C60): Set -7.5 to be displayed when the analog input value on terminal
[12] is 0%.
*The display unit should be selected with C58.
C61
Analog Input Adjustment for Terminal [C1] (Bias value)
C61 specifies a bias value to Reference frequency 2 and analog input monitor terminal [C1].
For details, refer to the description of F01.
C62
Analog Input Adjustment for Terminal [C1] (Bias base point)
C62 specifies a bias base point for Reference frequency 2 and analog input monitor terminal
[C1]. For details, refer to the description of F01.
6.3 Details of Function Codes
6-133
(Refer to F01.)
(Refer to F01.)