6.3.12 d codes (Application functions 2)

d51, d55,
Reserved for particular manufacturers
d69, d98,
d99
Function codes d51, d55, d69, d98 and d99 appear on the monitor, but they are reserved for
particular manufacturers. Unless otherwise specified, do not access these function codes.

6.3.13 U codes (Customizable logic functions)

U00
Customizable Logic (Mode selection)
U01 to U70
Customizable Logic: Step 1 to 14 (Setting)
U71 to U77
Customizable Logic Output Signal 1 to 7 (Output selection)
U81 to U87
Customizable Logic Output Signal 1 to 7 (Function selection)
U92 to U97
Customizable Logic Conversion Coefficients
The customizable logic function allows the user to form logic circuits and calculation circuits
with respect to digital and analog I/O signals, process signals arbitrarily, and establish
simplified relay sequences in the inverter.
In the customizable logic, the following can be specified as one step (component) to establish
sequences using 14 steps in total:
(1) Digital 2 inputs/digital 1 output + logic calculation (including timer)
(2) Analog 2 inputs/analog 1 output/digital 1 output + value calculation
(3) Analog 1 input/1 digital input/analog 1 output + value calculation/logic calculation
Specifications
Input signal
Operation block
Output signal
Number of steps
Customizable logic output
signal
Customizable logic processing
time
Item
Digital 2 inputs
Logical operation,
counter, etc.:
13 types
Timer: 5 types
Digital 1 output
14 steps
7 outputs
5 ms
6-249
6.3 Details of Function Codes
Specifications
Analog 1 input
Analog 2 inputs
Digital 1 input
23 types such as
value calculation,
6 types such as
comparator and
selector and hold
limiter
Analog 1 output/
Analog 1 output
digital 1 output

Hide quick links: