Fuji Electric FRENIC-HVAC User Manual page 479

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

H89 to H90
Reserved
These function codes and their data appear on the LCD monitor, but they are reserved for
particular manufacturers. Do not access them.
H91
Current Input Wire Break Detection
Using terminal [C1] (current input) enables wire break detection and alarm (CoF) issuance.
H91 specifies whether to enable the wire break detection, and the duration of detection. (The
inverter judges an input current of less than 2 mA on terminal [C1] as a wire break.)
- Data setting range: OFF (Disable alarm detection)
H92, H93
Continuity of Running (P and I)
Refer to the description of F14.
H94
Cumulative Motor Run Time 1
Refer to the description of H78.
H95
DC Braking (Braking response mode)
Refer to the descriptions of F20 through F22.
0.1 to 60.0 s (Detect wire break and issue CoF alarm within the time)
6-169
6.3 Details of Function Codes
(
Refer to F14.)
(
Refer to H78.)
(Refer to F20 through F22.)