Table 4.1 Currents Flowing through Inverter (continued)
Nominal applied
Power supply
motor
voltage
(HP)
1
2
3
5
7.5
10
15
20
25
30
40
50
60
Three-phase
75
460 V
100
125
150
200
250
300
350
450
500
600
800
900
1000
Note: A box () replaces an alphabetic letter depending on the enclosure.
M (NEMA/UL TYPE 1) or L (NEMA/UL TYPE 12)
Note: The input RMS current values listed in the above table apply when the inverter is connected with a power
supply of 460 V, 60 Hz, Rsce = 120.
If the power supply voltage differs from 460 V, such as 380 V, the input RMS current values will vary in
inverse proportion to the voltage.
Inverter type
Input RMS current
FRN001AR1-4U
FRN002AR1-4U
FRN003AR1-4U
FRN005AR1-4U
FRN007AR1-4U
FRN010AR1-4U
FRN015AR1-4U
FRN020AR1-4U
FRN025AR1-4U
FRN030AR1-4U
FRN040AR1-4U
FRN050AR1-4U
FRN060AR1-4U
FRN075AR1-4U
FRN100AR1-4U
FRN125AR1-4U
FRN150AR1S-4U
FRN200AR1S-4U
FRN250AR1S-4U
FRN300AR1S-4U
FRN350AR1S-4U
FRN450AR1S-4U
FRN500AR1S-4U
FRN600AR1S-4U
FRN800AR1S-4U
FRN900AR1S-4U
FRN1000AR1S-4U
4-3
4.2 Selecting Wire Size
460 V, 60 Hz
DC link bus current
(A)
(A)
1.4
1.8
2.7
3.4
3.8
4.7
6.5
8.0
9.0
11.1
12.1
14.9
18.0
22.1
24.3
29.8
30.0
36.8
35.8
43.9
48.5
59.5
60.4
74.0
72.3
88.6
88.7
109
119
146
141
173
175
215
207
254
249
305
311
381
340
417
435
533
547
670
614
752
767
940
970
1189
1093
1339

Hide quick links: