< Mode for measuring for a fixed period of time >
Fref
0.00
Hz
STOP
Iout
0.00A
PWR
0.03kW
↓
PRG
1.Start-up
2.Function Code
3.INV Info
4.Alarm Info
5.User Config
6.Tools
↓
/
PRG>6
1.PID Monitor
2.Multi-Op. Mon
3.CLogic Monitor
4.Resonant Avd.
5.Load Factor.
6.COM Debug
↓
/
PRG>6>5
Time
RUN→STOP
01h 00m 00s
0.00A
Imax
0.00A
Iave
0.0%
BPave
Standby
↓
/
PRG>6>5
Time
RUN→STOP
01h 00m 00s
0.00A
Imax
0.00A
Iave
0.0%
BPave
Standby
↓
/ / /
L.Factor Measure
PRG>6>5
RUN→STOP
Time
00h 30m 12s
0.00A
Imax
0.00A
Iave
0.0%
BPave
Executing...
↓
PRG>6>5
RUN→STOP
Time
01h 00m 00s
289.4A
Imax
182.2A
Iave
24.0%
BPave
Standby
1. Press the
2. Use the
3. Use the
4. On the mode selection screen, use the
Maximum output current
←
Average output current
←
Average braking power
←
consumption
5. Shift with the
<Initial setting value>
←
1 hour
←
6. While measuring, the message "L. Factor
Blinks while
measuring
Remaining
←
measurement
7. Measurement is concluded after the
5-94
Return to previous screen
key while the running mode
screen is displayed.
/
keys to select [6. Tools],
and confirm with the
/
keys to select [5. Load
Factor], and confirm with the
to move the Cursor, and select "Time".
Confirm with the
key.
/
, and set the
measurement time with the
Use the
key to start measurement.
Note: Pressing the
key while measuring
will cancel the measurement.
Measure" blinks.
measurement time elapses, and measurement
results are displayed.
Return to running
key.
key.
/
/
keys.